YTA80
The YTA80 is a head mount type of temperature transmitter
that accepts thermocouple, RTD, ohms or DC milivolts input
and converts it to digital communication signal based on
FOUNDATION Fieldbus protocol.
The YTA80 conforms to the standard DIN formB head mounting.
- Download General Specifications YTA80 here
- Download Instruction Manual YTA80 here
- Download Fieldbus Device Files (DD and CF) here
Common specifications:
The YTA80 conforms to the standard DIN formB head mounting.
- Download General Specifications YTA80 here
- Download Instruction Manual YTA80 here
- Download Fieldbus Device Files (DD and CF) here
Common specifications:
| Supply voltage, DC: Standard, YTA80/KN2: | 9 – 32V |
| ATEX, YTA80/KS2: | 9 – 30V |
| In FISCO installations: | 9 – 17.5V |
| Consumption: | < 11mA |
| Max.current increase in the event of an error: | < 7mA |
| Isolation voltage, test: | 1.5kVAC for 60sec |
| Isolation voltage, operation: | 50VRMS/75VDC |
| Warm-up time: | 30sec |
| Signal/noise ratio: | min.60dB |
| Response time (programable): | 1 – 60 sec |
| Updating time: | < 400ms |
| Execution time, PID controller: | <200msec |
| Execution time, analogue input: | <50msec |
| Signal dynamics, input: | 24 bit |
| Calibration temperature: | 20 – 28ºC |
| Ambient temperature limits: | |
| (Option code may affects limit) | -40ºC to +85ºC |
| Vibration: | IEC 60068-2-6 and IEC60068-2-64 |
| Lloyd’s specification no.1: | 4g/2 – 100Hz |
| Humidity: | < 95%RH (non-cond.) |
| Tightness (enclosure / terminal): | IP68/IP00 |
| Weight: | 55g |


The powerful line-up of DPharp digital family is launched.
The world's smallest dual bent tube Coriolis Mass Flowmeter


The highlights of DPharp unique technologies that provides superior performance, stability and reliability in your measurement.
- EJX B Series Differential Pressure/Pressure Transmitters
Yokogawa's versatile field device management tool FieldMate is a so called hybrid solution supporting both EDDL as well as FDT/DTM technology.