EJX130A Differential Pressure Transmitter |
| M Capsule |
H Capsule |
| Range |
-100 to 100 kPa
(-400 to 400 inH2O) |
-500 to 500 kPa
(-2000 to 2000 inH2O) |
| Span |
1 to 100 kPa
(4 to 400 inH2O) |
5 to 500 kPa
(20 to 2000 inH2O) |
| Accuracy |
±0.04% |
| Degrees of protection |
IP67, NEMA 4X, and JIS C0920 immersion proof |
| Certificates |
FM, CENELEC ATEX, CSA, IECEx |
| Output |
4 to 20 mA DC or FOUNDATION Fieldbus™, 2-wire system with digital communication |
| Supply voltage |
BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type) Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity and 9 to 17.5 V DC for FISCO) |
| Ambient temperature |
-40 to 85 deg C (-40 to 185 deg F) (general use type)
-30 to 80 deg C (-22 to 176 deg F) (with integral indicator) |
| Process temperature |
-40 to 120 deg C (-40 to 248 deg F) (general use type) |
| Maximum working pressure |
32 MPa
(4500 psi) |
| Mounting |
2-inch pipe mounting |
| Wetted parts material |
Capsule |
316L SST(Diaphragm material is Hastelloy C-276) |
| Cover flange |
ASTM CF-8M |
| Housing |
Cast aluminum alloy or ASTM CF-8M stainless steel (optional) |