| Accuracy (typical) |
YTA110: ±0.1% of span YTA310/320: ±0.05% of span |
| Cold junction Compensation accuracy |
(For T/C only) ±0.5 deg C (0.9 deg F) |
| Power supply effect |
±0.005% of calibration span per volt |
| Ambient temperature effect |
±0.1%/10 deg C (YTA110) |
| Input signal |
YTA110/YTA310: single input, YTA320: dual input Input type is selectable: thermocouples, 2-, 3-, and 4-wire RTDs, ohm and DC milivolt |
| Output |
Two wire 4 to 20 mA DC or FOUNDATION fieldbus signal (YTA320) |
| Supply voltage |
BRAIN and HART: 10.5 to 42 V DC
(10.5 to 30 V DC for Intrinsically safe type)
Fieldbus: 9 to 32 V DC
(9 to 24 V DC for Entity and 9 to 17.5 V DC for FISCO) |
| Ambient temperature |
Option code may affect limits
-40 to 85 deg C (-40 to 185 deg F)
-30 to 80 deg C (-22 to 176 deg F) with integral indicator |
| Mounting |
Optional mounting bracket can be used either for two-inch pipe or flat panel mounting. |
| Weight |
1.2 kg (2.6lb) without integral indicator and mounting bracket. Integral indicator weighs 0.2kg (0.4lb). |
| Degrees of protection |
IP66, IP67 and NEMA 4X |
Certificates |
CENELEC, CSA, FM, SAA or TIIS |
| SIL Certificate
|
Certified by TÜV NORD in compliance with the IEC61508 SIL 2 capability for single transmitter use. |