Parameter
|
Specification
|
| Method of detection |
Mean value |
| Display |
LCD |
Digital display: 3200 counts |
| Bar-graph display: 32 segments |
| Range Switching |
Auto-range |
| Ambient temperature and humidity |
0 to 50 deg.C, 80% RH or less (no condensation)) |
| Temperature Coefficient |
0.05% of range/deg.C or less(within the ranges of 0 to 18 deg.C and 28 to 50 deg.C for measurement of 0 to 50 A)
|
| Influence of external magnetic field |
0.0005% typical*1 (on current value of adjacent cable) |
| Influence of conductor position |
Within accuracy |
| Safety Standard |
Approved for conformity to EN 61010-1, EN 61010-2-032 |
| Circuit Voltage |
300Vrms or less |
| Withstanding Voltage |
3.7kV AC for one minute |
| Power Supply |
One CR2032 (Coin-shaped) 3 V battery |
| Battery Life |
Approx. 90 hours (when continuously used) |
| Auto power-off |
Approx. 10 minutes |
| Diameter of measurable conductor |
40 mm at maximum |
| Dimensions |
Approx. 70(W) × 176(H) × 25(D) excluding protrusions |
| Weight |
Approx. 200g |
| Accessories |
Instruction manual, battery, soft case |