Parameter |
Specification |
| Method of detection |
Mean value detection and rms-value calibration |
| Display |
LCD |
Digital display: 3200 counts |
| Bar-graph display: 32 segments |
| Range Switching |
Range selection Auto or Manual
|
| Data hold |
On all ranges
|
| Operating temperature and humidity |
0 to 50 deg.C, 80% RH or less (no condensation) |
| Temperature Coefficient |
Following values must be added in the temperature range of either
0 to 18℃ or 28 to 50℃.
0<1<50.0A: ±(0.08% of reading /℃ + 0.5 digits/℃)
50.0<1<60.6A:±(0.3% of reading/℃ + 0.5 digits/℃)
|
| Effect of external magnetic field |
0.0005% typical value (in terms of magnitude of current in adjacent wires) |
| Safety Standard |
Conforms to EN 61010-1, EN 61010-2-032 CAT.III 300V
Circuit voltage: 300 V rms or less
|
| Circuit Voltage |
300Vrms or less |
| Withstanding Voltage |
3.7kV AC for one minute |
| Power Supply |
One CR2032 (Coin-shaped) 3 V battery |
| Power consumption |
6 mW max |
| Battery Life |
Approx. 90 hours |
| Automatic power-off |
power approx. 10 minutes after the last switch operation |
| Diameter of measurable conductor |
40 mm at maximum |
| Dimensions |
Approx. 70(W) × 179(H) × 25(D) excluding protrusions |
| Weight |
Approx. 200g |
| Accessories |
User's manual, battery, soft carrying case (RB057)
|