Testing Performance Specifications
| Model |
Testing Voltage |
AC Voltage |
Continuity Range |
| 2404 13 |
500V/100MΩ |
0 to 300V |
0 to 500Ω |
| 2404 14 |
500V/1000MΩ |
0 to 500Ω |
| 2404 15 |
1000V/2000MΩ |
Not provided |
| 2404 16 |
2000V/5000MΩ |
Not provided |
- Accuracy
- Insulation resistances measurement:
±5% of indicated value in effective measuring range 1, ± 10% of indicated value in effective measuring range 2, less than ± 0.7% of scale length at zero and infinity. AC voltage measurement ±10% of full scale
- Low resistance measurement:
Less than 5% of full scale.
- Scale Length:
Approx. 88 mm (3-1/2")
- Measuring Terminal Voltage:
More than 90% of testing voltage at center scale, or ±10% of testing voltage at infinity (at handle speed of more than 120 rpm)
- Rotating Speed of Handle :
More than 120 rpm
- Case:
Polycarbonate resin, green-yellow
- Dielectric Strength:
2000V AC (100 to 1,000V models), or 3,000V AC (2,000V models) for one minute between electric circuits and case/handle.
|