Skip navigation
Go to Global Navigation
Go to Primary Contents
Go to Site Information

YOKOGAWA

Yokogawa Electric Corporation

Analog Output Module

Analog Output Module (F3DA02-0N/F3DA04-1N/F3DA08-5N)

  -The output signal ranges from -10 to 10 V DC or from 4 to 20 mA DC.
  -A single module can accommodate two(F3DA02-0N)/four(F3DA04-1N)/eight(F3DA08-5N)
 output points.
  -Provides a conversion period (output update period) as high as 2 ms(F3DA02-0N)/4 ms
 (F3DA04-1N/F3DA08-5N).
  -Provided with an easy-to-use scaling feature.
  -The user can select either a hold output or a preset output for each channel if the CPU
 fails. (F3DA04-1N/F3DA08-5N)
Item
F3DA02-0N
F3DA04-1N
F3DA08-5N
Number of I/O points
2
4
8
Output signal range


-10 to 10V DC 4 to 20mA DC *1 (one line common, Floating type)

-10 to 10V DC *1
(one line common, floating type)

Isolation method

Isolated by Photocouplers

Allowable load resistance

5 kΩ or more for voltage output /600 Ωor less for current output

5 kΩ or more
Resolution
(12bit A/D or D/A)

5.7 mV for voltage output, 5.7 μA for current output

5.7 mV

Overall accuracy
23±2°C: ±0.2% of F.S.
0 to 55°C: ±0.5% of F.S.
Conversion speed 2 ms (fixed) 24V DC ±10% , 150mA
4 ms (fixed) 24V DC ±10% , 180mA
Scaling

Upper and lower limit values can be set to any values between -20,000 and 20,000

*1: The actual time constant value depends on the number of channels not skipped and other settings.