Module Specifications 1/2

Performance

Previous

Item Specifications
F3SP08 F3SP21 F3SP28 F3SP38 F3SP53 F3SP58
Control method Repeating operation (by stored program)
I/O control method Refresh method / Direct I/O command
Programming language Structured-ladder language, object ladder language, mnemonic language
Number of I/O points Max. 2048 Max. 2048 Max. 4096 Max. Max. 8192
(including remote I/O)
Max. 4096 Max. 8192
(including remote I/O)
Program capacity
(ROM can be used)
Max. 10K steps Max. 30K steps Max. 120K steps Max. 56K steps Max. 120K steps
Number of program blocks Max. 32 Max. 1024
Number of instructions Basic
instruction
25 types 33 types
Application instruction 227 types 312 types
Instruction execution time Basic
instruction
0.18 to 0.36 μs
/instruction
0.045 to 0.18 μs
/instruction
0.0175 to 0.07 μs
/instruction
Application instruction 0.36 μs
/instruction or longer
0.18 μs
/instruction or longer
0.07 μs
/instruction or longer
Scan time observation time 10 to 200ms variable (settable on 1ms basis)
Power-on or restoration of
power after power failure
Auto start, auto restart (auto recording of power ON/OFF time and momentary power failure occurrence time)
Other functions
  • Sensor control function*1 (scan time 200 μs to 25 ms)
  • Configuration function (device capacity, data lock-up range at power failure, designation of output at error)
  • Constant scan function (1ms to 190 ms, settable on 0.1 ms basis)
  • Debug function (forced set/reset, online edit etc.)
  • Error log save function (64 items), user-definable log save function
  • Data/clock function (year/month/day/hour/minute/second/day of the week)
  • Program protect function
  • Program data write to ROM
  • Sampling trace function*1
  • Personal computer link function (transmission rate 115K bps*1 )

*1: Not available with F3SP08 and F3SP21