JUXTA F Series Signal Conditioners
Specifications
| Construction | Front-terminal type |
|---|---|
| Mounting Method: | DIN-rail mounting, rack mounting or wall mounting |
| Connection Method: | M4 screw terminal |
| External Dimensions: | 72×24×127 mm (H×W×D) |
| Power Requirements: | 24 V DC±10% |
Signal Conditioners
| Model | Product Name | Input Type | Output Type | Descriptions |
|---|---|---|---|---|
| FA1A/V | Distributor | 4 to 20 mA DC, from 2-wire type transmitter | DC Voltage or DC Current | |
| FA4A/V | Distributor (Non-isolated) |
1 to 5 V DC or 4 to 20 mA DC | Non-isolated output | |
| FA5A/V | Distributor (with Square Root Extractor) |
DC Voltage or DC Current | Field configurable | |
| FA0A | Output Isolator | 1 to 5 V DC | DC Current | 1500 V AC (1 min.) of withstand voltage for output signal. |
| FC0A | Output Isolator | 4 to 20 mA DC | 4 to 20 mA or 10 to 50 mA DC | |
| FH0V | Output Isolator | 1 to 5 V DC | DC Voltage | |
| FC1A/V | Loop Powered Isolator | DC Current | 1 to 5 V DC or 4 to 20 mA DC | Fixed range Loop powered |
| FH1A/V | Isolator | DC Voltage or DC Current | DC Voltage or DC Current | Fixed range |
| FH2A/V | Isolator (Free Range Type) |
Free range Field configurable |
||
| FH3A/V | Isolator (High Speed Response Type) |
15 msec. conversion for 63% response | ||
| FHRA/V | Isolator (Reverse Output Type) |
Fixed range | ||
| FH4A/V | DC Converter (Non-isolated) |
Non-isolated output | ||
| FH5A/V | Isolator (Square Root Extractor) |
1 to 5 V DC | Field configurable | |
| FM1A/V | Isolator (mV Input Free Range Type) |
DC mV Signal | Field configurable | |
| FR5A/V | RTD Converter (Free Range Type) |
Resistance Temperature Detector (RTD) | DC Voltage or DC Current | Field configurable |
| FT5A/V | Thermocouple Converter (Free Range Type) |
Thermocouple | DC Voltage or DC Current | Field configurable |
| FS1A/V | Potentiometer Converter (Free Range Type) |
Potentiometer resistance(3-wire type) | DC Voltage or DC Current | Field configurable |
| FP1P | Pulse Repeater | Contact Pulse, Voltage Pulse or Current Pulse | Open collector | Pulse rate fixed in 1:1 |
| FP4P | Pulse Rate Converter | Contact Pulse or Voltage Pulse | Open collector or Contactless AC switch | Field configurable pulse rate (by internal switch) |
| FQ1A/V | Pulse to Analog Converter | Contact Pulse, Voltage Pulse or Current Pulse | DC Voltage or DC Current | Fixed range |
| FQ2A/V | Pulse to Analog Converter (Free Range Type) |
Free range Field configurable | ||
| FQ0P | Analog to Pulse Converter | DC Voltage or DC Current | Open collector or Contactless AC switch | Fixed range |
| FQ2P | Analog to Pulse Converter (Free Range Type) |
Free range Field configurable | ||
| FB1A/V | CT Converter (R.M.S) |
AC Current from CT | DC Voltage or DC Current | R.M.S. conversion |
| FB3A/V | AC Current Converter (RMS) | AC Current | R.M.S. conversion | |
| FG1A/V | PT Converter (RMS) | AC Voltage from PT | R.M.S. conversion | |
| FG3A/V | AC Voltage Converter (RMS) | AC Voltage | R.M.S. conversion | |
| FD1A/V | Tachometer Converter | AC Voltage from tachometer | Mean value conversion | |
| FF1A/V | Pneumatic to Electrical Converter | Pneumatic Signal | DC Voltage or DC Current | Input signal range: 0.2 to 1.0 kg/cm2, 3 to 15 psi or 20 to 100 kPa |
| FF1T | Pneumatic to Electrical Converter (2-wire System) |
4 to 20 mA DC | ||
| FV1A/V | Manual Setter | Manual Setting | DC Voltage or DC Current | With monitoring output |
| FVDV | Voltage Divider | AC/DC Voltage signal | AC/DC Voltage signal | Dividing ratio 1000:1 |