Yokogawa Electric Corporation

JUXTA M Series Signal Conditioners

Specifications

Common Specifications

Construction Plug-in type (Main unit with Socket)
Mounting Method: Wall mounting or DIN-rail mounting
Connection Method: M3.5 screw terminal
External Dimensions: 1 output type: 85×50×123 mm (H×W×D)
2 outputs type: 85×50×132 mm (H×W×D)
Power Requirements:
(Also refer to the below table)
Type 1: 12 to 48 V DC or 85 to 264 V AC
Type 2: 85 to 132 V AC/24V DC or 180 to 264 V AC
Type 3: 24 V DC±10%, 85 to 132 V AC/85 to 150 V DC or 170 to 264 V AC
Type 4: 85 to 132 V AC or 170 to 264 V AC

Signal Conditioner

Model Product Name Input Type Output Type Power Supply Descriptions
MA1 Distributor 4 to 20 mA DC, from 2-wire type transmitter DC current or DC voltage
signal
Type 1 1-output type
MA5 Distributor (Free Range Type) Type 1 Free range type
MA4 Distributor
(Non-isolated)
Type 1 Non-isolated output
MA5D Distributor (2-output, Free Range Type) Type 1 2-output, free range type
MHF Isolator
(Super Speed Response Type)
DC Voltage or DC Current DC current or DC voltage
signal
Type 3 50 μsec. conversion for 63% response
MH1 Isolator Type 1 1-output type
MH5 Isolator (Free Range Type) Type 1 Free range type
MH1D Isolator
(2-output Type)
Type 1 2-output type
MH5D Isolator
(2-output, Free Range Type)
Type 1 2-output, free range type
MC1B Loop Powered Isolator (Dual Channels) 4 to 20 mA DC 4 to 20 mA DC Not required 2 channels type
MU5 Universal Temperature Converter (Free Range Type) Thermocouple, RTD, mV DC signal DC current or DC voltage
signal
Type 1 Free range type
MU5D Universal Temperature Converter (2-output, Free Range Type) Type 1 2-output, free range type
MS5 Potentiometer Converter (Free Range Type) Potentiometer resistance change
(3-wire
type)
DC current or DC voltage
signal
Type 1 Free range type
MS5D Potentiometer Converter (2-output, Free Range Type) Type 1 2-output, free range type
MP1 Pulse Repeater Contact Pulse, Voltage Pulse or Current Pulse Open collector or Contactless AC switch Type 3 Pulse rate fixed in 1:1
MP4 Pulse Rate Converter Type 3 Field configurable pulse rate, etc.
MQ1 Pulse to Analog Converter DC Voltage or DC Current Type 1 Fixed range type
MQ2 Pulse to Analog Converter (Free Range Type) Type 3 Field configurable input / output range, etc.
MQ0 Analog to Pulse Converter DC Voltage or DC Current Open collector or Contactless AC switch Type 3 Fixed range type
MB1 CT Converter (RMS) AC Current from CT DC Voltage or DC Current Type 1 1 A or 5 A AC input
MG1 PT Converter (RMS) AC Voltage from PT Type 1 110 V or 150 V AC input
MD1 Tachometer Converter AC Voltage from tachometer Type 1 Mean value conversion of AC/DC.
ML2 RS232C/RS485 Converter RS232C/RS485 dual directional communication Type 3 Applicable baud rate: 300 to 38400 bps.
MLC Load Cell Converter Load cell signal DC Voltage or DC Current Type 3 With remote sensing function