JUXTA M Series Signal Conditioners
Specifications
Common Specifications
| Construction | Plug-in type (Main unit with Socket) |
|---|---|
| Mounting Method: | Wall mounting or DIN-rail mounting |
| Connection Method: | M3.5 screw terminal |
| External Dimensions: | 1 output type: 85×50×123 mm (H×W×D) |
| 2 outputs type: 85×50×132 mm (H×W×D) | |
| Power Requirements: (Also refer to the below table) |
Type 1: 12 to 48 V DC or 85 to 264 V AC |
| Type 2: 85 to 132 V AC/24V DC or 180 to 264 V AC | |
| Type 3: 24 V DC±10%, 85 to 132 V AC/85 to 150 V DC or 170 to 264 V AC | |
| Type 4: 85 to 132 V AC or 170 to 264 V AC |
Signal Conditioner
| Model | Product Name | Input Type | Output Type | Power Supply | Descriptions |
|---|---|---|---|---|---|
| MA1 | Distributor | 4 to 20 mA DC, from 2-wire type transmitter | DC current or DC voltage signal |
Type 1 | 1-output type |
| MA5 | Distributor (Free Range Type) | Type 1 | Free range type | ||
| MA4 | Distributor (Non-isolated) |
Type 1 | Non-isolated output | ||
| MA5D | Distributor (2-output, Free Range Type) | Type 1 | 2-output, free range type | ||
| MHF | Isolator (Super Speed Response Type) |
DC Voltage or DC Current | DC current or DC voltage signal |
Type 3 | 50 μsec. conversion for 63% response |
| MH1 | Isolator | Type 1 | 1-output type | ||
| MH5 | Isolator (Free Range Type) | Type 1 | Free range type | ||
| MH1D | Isolator (2-output Type) |
Type 1 | 2-output type | ||
| MH5D | Isolator (2-output, Free Range Type) |
Type 1 | 2-output, free range type | ||
| MC1B | Loop Powered Isolator (Dual Channels) | 4 to 20 mA DC | 4 to 20 mA DC | Not required | 2 channels type |
| MU5 | Universal Temperature Converter (Free Range Type) | Thermocouple, RTD, mV DC signal | DC current or DC voltage signal |
Type 1 | Free range type |
| MU5D | Universal Temperature Converter (2-output, Free Range Type) | Type 1 | 2-output, free range type | ||
| MS5 | Potentiometer Converter (Free Range Type) | Potentiometer resistance change (3-wire type) |
DC current or DC voltage signal |
Type 1 | Free range type |
| MS5D | Potentiometer Converter (2-output, Free Range Type) | Type 1 | 2-output, free range type | ||
| MP1 | Pulse Repeater | Contact Pulse, Voltage Pulse or Current Pulse | Open collector or Contactless AC switch | Type 3 | Pulse rate fixed in 1:1 |
| MP4 | Pulse Rate Converter | Type 3 | Field configurable pulse rate, etc. | ||
| MQ1 | Pulse to Analog Converter | DC Voltage or DC Current | Type 1 | Fixed range type | |
| MQ2 | Pulse to Analog Converter (Free Range Type) | Type 3 | Field configurable input / output range, etc. | ||
| MQ0 | Analog to Pulse Converter | DC Voltage or DC Current | Open collector or Contactless AC switch | Type 3 | Fixed range type |
| MB1 | CT Converter (RMS) | AC Current from CT | DC Voltage or DC Current | Type 1 | 1 A or 5 A AC input |
| MG1 | PT Converter (RMS) | AC Voltage from PT | Type 1 | 110 V or 150 V AC input | |
| MD1 | Tachometer Converter | AC Voltage from tachometer | Type 1 | Mean value conversion of AC/DC. | |
| ML2 | RS232C/RS485 Converter | RS232C/RS485 dual directional communication | Type 3 | Applicable baud rate: 300 to 38400 bps. | |
| MLC | Load Cell Converter | Load cell signal | DC Voltage or DC Current | Type 3 | With remote sensing function |