Category Sitemap
Home / Our Businesses / Controllers & Data Acquisition / Products / Paperless Recorders /
Paperless Videographic Recorders

DX100/DX200
Applications
  1 2 3 4 5  
Equipped with a Log display function for continuous monitoring of radiation levels around the premises of facilities such as power plants, and a simulation function for operation and control training. Use a replacement for SRHD NRE, and mR device.
Log Display Function for Continuous Monitoring of Radiation level
Not only trend display and digital value but also log scale make you read data instantly. This signal unit can provide all information that in the field of continuous monitoring radiation levels.

Special Function Specification Code: /S13
Input and digital value display specification

Input Range: DC voltage input (DCV: 20/60/200 mV, 26/20 V) voltage value, display span min. value > display span max. value
Scaling Range: 1.0E_15-1.0E+15
Max. 15 decades
Scale value: exponent min. value < exponent max. value
Data Display Range: 1.0E_15-1.0E+15
(within the same decade, 1.0Elll-9.9Elll)
Number of displayed mantissa digits, able to select 2 or 3 digits (in basic setting mode).
3 digit time 1.0E_15-1.0E+15
Units: Optional setting available (up to 6 characters)
Alarm: H/L/T/t only
Set alarm values using voltage values. Alarm hysteresis fixed at 0%.
Relationship between input voltage and digital value display
The relationship between the input voltage of the LOG specific range and the digital display value is shown as follows:
input voltage Display
Simulation Function for Operation and Control Training
To maintain continuous safe operations, operation and control training is essential. To support such training activities, we've created a simulation function. The screen update stop (trend, digital values, bar graphs, etc.) can be controlled during training via remote control or communications commands.

Special Function Specification Code: /S14
Screen display update
Input a signal to the remote control terminal (/R1), or use a communications command to stop the screen display update.



Clearing the internal memory/displayed waveform
In inputting a signal to the remote control terminal, or using communication commands to clear the internal memory, you can also clear the displayed trend waveform. When the remote control terminal's input signal changes from open to close, both the internal memory and the trend waveform are cleared.

Centerscale Display Function for Monitoring Power Frequency
To maintain stable power supply, you must monitor the power frequency fluctuations. To support your monitoring, we've included a scale display function which centers the display at the power frequency (50 Hz/60 Hz).

Special Housing for SRHD, NRE, and mR100F Compatible
DX100L You can replace recorders with non-SRHD, NRE, and mR100F panel cut and depth dimensions. Also, the terminal position from the panel is almost the same as SRHD, NRE, and mR100F, so wiring and other changes of replacement can be carried out with ease.

dimensions
GLOBAL  
YOKOGAWA

Powered by Ultraseek
·  DX100/DX200
Supports
Related Products
Top of this page