Frequently Asked Questions

Green Series

Connection/Setup/Monitor

Questions

Connection

1.  What is the port for the LL100/200-specific cable on the PC side?
2.  How about Ethernet support?
3.  What UT series products support Ethernet?
4.  What are the protocol choices when communicating via Ethernet on an instrument with RS485 communication using the UT351/UT551 gateway function?
5.  What is the IP address?
6.  The IP address item shows *.*.*.*,* when I call the parameter, but isn't the address specified with 4 parts?

Setup

1.  When I first turn ON the power the manual says IN should be displayed but it isn't displayed.
2.  I want to change the input type.
3.  Can I change setup parameters during operation?
4.  I can't set contact input registration DI or contact output registration DO.
5.  What are direct and reverse action?
6.  What about CT settings during current control output?
7.  There is no current input range, why is that?

Monitor

1.  How many units can be monitored with the multi-monitor function?
2.  What types can be recorded with the multi-monitor function?
3.  What is the output format of recorded data?


Answers

Connection

1. What is the port for the LL100/200-specific cable on the PC side?
It is RS232C. It is a D-Sub, 9-pin connector.

Top of this page

2. How about Ethernet support?
Supported. A separate VJET or other RS485/Ethernet converter is required. Also, the controller must have a communication option.

Top of this page

3. What UT series products support Ethernet?
The UT351 and UT551.

Top of this page

4. What are the protocol choices when communicating via Ethernet on an instrument with RS485 communication using the UT351/UT551 gateway function?
Select MODBUS RTY(PLS=8).
5. What is the IP address?
In general, the private address 192.168.0.0 is used. When connecting the unit to an in-house network, consult with your network administrator.

Top of this page

6. The IP address item shows *.*.*.*,* when I call the parameter, but isn't the address specified with 4 parts?
When accessing a controller connected by RS485 communications via the UT351/551 gateway function, the last ,* is the address setting for the destination controller. Also, note that a comma is used rather than a period.

Top of this page


Setup

1. When I first turn ON the power the manual says IN should be displayed but it isn't displayed.
If you set inputs even just once, it is no longer displayed when the power is turned ON.

Top of this page

2. I want to change the input type.
When you change the input, the parameters are initialized. You should especially avoid changing during operation.

Top of this page

3. Can I change setup parameters during operation?
If you change setup parameters, parameters may be initialized. You should not change them during operation.

Top of this page

4. I can't set contact input registration DI or contact output registration DO.
These cannot be set when in custom computation mode.

Top of this page

5. What are direct and reverse action?
In general, heating control is called reverse action and cooling control is called direct action. With reverse action, when PV is smaller than SP output is ON, and with direct action, when PV is larger than SP output is ON.

Top of this page

6. What about CT settings during current control output?
These settings are ignored even if entered.

Top of this page

7. There is no current input range, why is that?
For inputting current, resistance is used and voltage is input.

Top of this page


Monitor

1. How many units can be monitored with the multi-monitor function?
In terms of numbers of loops, 16 loops worth in total. If one controller is performing cascade control, that would be 2 loops worth being used on one unit, so up to 8 units could be connected.

Top of this page

2. What types can be recorded with the multi-monitor function?
PV, SP, OUT, and alarms.

Top of this page

3. What is the output format of recorded data?
It is output to a CSV file.

Top of this page