Category Sitemap
Home / Our Businesses / Controllers & Data Acquisition / Service & Support / FAQ /
Frequently Asked Questions

Software
DAQEXPLORER
Questions
Cable
Connection
Error
File conversion
File transfer
Supported OS
Version
Viewer
Questions and Answers
Cable
-To connect the DX100 directly to a PC, use one cross cable.
-To connect the DX100 to a PC via a hub, two straight cables are required.
Top of this page
Connection
You can delete data files from external media by dragging them to the recycle box on the DAQEXPLORER desktop. Data files in internal memory cannot be deleted.
Top of this page
With the PC and DX connected to a LAN, the IP address, subnet mask, and default gateway of both instruments must be set correctly, and then the following procedure is performed.
  1. Launch the DAQWORX DAQEXPLORER Desktop.
  2. Input the user name and password. If the login funcion is activated on the DX, please check the user name and password on the DX.
  3. Choose File > New mount, then specify the IP address of the DX.
  4. The icon of the specified DX is mounted. Double-click the icon.
Top of this page
Yes. They are set manually using the Set time.
Top of this page
Error
There are a variety of possible causes for this. One possibility is that the network is not properly connected. Check all connections. Next, try starting DAQEXPLORER desktop using the user name and password set on the DX.
Top of this page
File conversion
Check the number of data. EXCEL worksheets have a size limitation of 65536 rows and 256 columns. If there are 65536 or more data along the time axis the data cannot be opened in EXCEL. For example, if data is recorded every second, one day's worth of recording will contain 86400 data, which exceeds the maximum number of rows. To prevent this, be sure to specify the time width during conversion to EXCEL.
Top of this page
This is possible using the DAQEXPLORER software program. Connect the DX100 or DX200 to a PC via Ethernet, and set DAQEXPLORER to send recorded data to the PC's hard disk and automatically convert them to EXCEL files.
Top of this page
They are created in the same folder specified for automatic file transfers.
Top of this page
Yes. Drag the file onto the EXLCONVERT icon on the DAQEXPLORER desktop. You can also drag multiple files at once for batch conversion.
Top of this page
Yes. If DAQEXPLORER is not running, automatic file transfer and conversion are not carried out.
Top of this page
File transfer
The automatic file transfer update interval is the interval at which the software checks for recorded data files from the DX, MV, or other instrument. If the check finds no untransferred data files, none are transferred. If recorded data files are created daily on the DX, MV, or other instrument, file transfer will also occur daily.
Top of this page
Supported OS
Yes, the latest version supports it.
Top of this page
The latest version (R4.09 or later) supports the Windows Vista Home Premium 32-bit, and Windows Vista Business 32-bit versions.
Top of this page
Version
A release upgrade for DAQEXPLORER is available.
Top of this page
Viewer
Display data files contain the minimum and maximum values from a single recording. In trend display, these minimum and maximum values are connected by vertical lines, resulting in thick trend lines.
Top of this page
GLOBAL  
YOKOGAWA

Powered by Ultraseek
FAQ
·  Software
Contact Form
If you can not find your answers here, please feel free to contact us.