- JUXTA M Series Signal Conditioners
Introducing Useful Functions
JUXTA M Series Signal Conditioners
![]()
Two functions are included that let you linearize any breakpoint (the VJ77 setting tool is useful for breakpoint settings).
[Affected Models]
MA5 Distributor (1-output), MA5D (2-output, isolated), MH5 Isolator (1-output), MH5D (2-output, isolated)
After starting the VJ77 and choosing Parameter setting > Set > SET, you can turn LINEARIZE "ON" in the SET(I/O) tab and specify breakpoints of the desired breakpoint table allowing operations with arbitrary breakpoints.
To enable calculation of square roots, set LINEARIZE to SQR. The low cut point (the point at which input at or below the specified percentage results in equivalent output) can be set to an arbitrary percentage using the LOW CUT item.