You can change the setting for the type of thermocouple, RTD, or mV signal sensor.

[Affected Models]
MU5 Universal Temperature Converter (1-output), MU5D (2-output, isolated)

[Setup Procedure]
After starting the VJ77 setting tool and choosing Parameter setting > Set > SET(I/O) tab, you can change the sensor type under SENSOR TYPE by selecting TC for thermocouple, RTD for resistance temperature detector, or mV for millivolt signals. Next, select the desired thermocouple or RTD sensor type under TC TYPE or RTD TYPE.

TC TYPE:
     JIS thermocouple K, T, E, J, R, S, B, or N
     ASTM E988 tungsten-Rhenium W3, W5
RTD TYPE:
     Pt100 (ITS-90, ITPS68), JPt100, Pt50

You can also change the sensor type setting using the JHT200 Handy Terminal. Using the JHT200 Handy Terminal, you can change to the desired sensor type by choosing SET > D:SET(I/O) > SENSOR TYPE > TC TYPE / RTD TYPE.