1.Setting for DI/DO
Parameters |
Names |
Setting Range |
| DIO16 |
DI1/DO6 Specification |
DI: Used as digital input
DO: Used as digital output |
| DIO25 |
DI2/DO5 Specification |
| DIO34 |
DI3/DO4 Specification |
| DIO43 |
DI4/DO3 Specification |
| DIO52 |
DI5/DO2 Specification |
| DIO61 |
DI6/DO1 Specification |
・Function selection for DI
Parameters |
Names |
Setting Range |
| DI1F |
DI1 function selection |
NONE: No function assigned
E-AUT: Switching to Automatic mode (status)
E-MAN: Switching to Manual mode (status)
E-O/C: Open/Close switching
E-L/R: Local/Remote switching
E-PMV: Preset MV switching
E-STC: STC start
E-SEL: Selector selection
TR-MPMV: Output preset and manual switching
TR-MAN: Manual switching (trigger)
TR-AUT: Automatic switching (trigger)
TR-CAS: Cascade switching (trigger)
LCD-OFF: LCD backlight OFF
E-TRK: Output tracking |
| DI2F |
DI2 function selection |
| DI3F |
DI3 function selection |
| DI4F |
DI4 function selection |
| DI5F |
DI5 function selection |
| DI6F |
DI6 function selection |
・Function selection for DO
Parameters |
Names |
Setting Range |
| DO1F |
DO1 function selection |
OFF: NONE
PH1: High limit alarm for PV1
PL1: Low limit alarm for PV1
HH1: High-high limit alarm for PV1
LL1: Low-low limit alarm for PV1
DL1: Alarm for deviation variable 1
VL1: Velocity alarm for PV1
PH2: High limit alarm for PV2
PL2: Low limit alarm for PV2
HH2: High-high limit alarm for PV2
LL2: Low-low limit alarm for PV2
DL2: Alarm for deviation variable 2
VL2: Velocity alarm for PV2
DL1VL1: DL1VL1: Alarm for deviation variable 1/Velocity alarm for PV1
DL2VL2: DL2VL2: Alarm for deviation variable 2/Velocity alarm for PV2
1-ALM: Logical OR of all loop 1 alarms
2-ALM: Logical OR of all loop 2 alarms
CAS: Cascade mode
CASAUT: Cascade or Automatic mode
O/C: Open/Close
L/R: Remote/Local |
| DO2F |
DO2 function selection |
| DO3F |
DO3 function selection |
| DO4F |
DO4 function selection |
| DO5F |
DO5 function selection |
| DO6F |
DO6 function selection |
2.Control type
Parameters |
Names |
Setting Range |
| CNT1 |
Control type |
PID: Standard PID control
S-PI: Sample-and-hold PI control
PD: Proportional (PD) control |
3.Analog output retransmission function
Parameters |
Names |
Setting Range |
| Y2S |
Analog output 2 selection |
OFF: No function assigned
PV1: Process variable 1
SV1: Setpoint value 1
PV2: Process variable 2
SV2: Setpoint value 2
MV: Manipulated output variable
X1: Analog input 1
X2: Analog input 2
X3: Analog input 3
X4: Analog input 4
X5: Analog input 5 |
| Y3S |
Analog output 3 selection |