- Home>
- Products & Solutions:
- Controllers, Recorders & Data Acquisition:
- Service & Support:
- One Point Lessons:
- MVAdvanced MV1000/MV2000:
- JUXTA M Series Signal Conditioners :
- MW100 Data Acquisition Unit:
- PR300 Power and Energy Meter:
- µR Series Industrial Intelligent Recorders :
- UTAdvanced Digital Indicating Controllers>
- UT/UP Series Digital Indicating Controllers:
- DXAdvanced DX1000/DX2000:
- YS1000 Series Single-loop Controllers:
- YS1000 Series Single-loop Controllers
Introducing Useful Functions
YS1000 Series Single-loop Controllers
![]()
Overview
The YS1500 Indicating Controller comes with a variety of built-in functions that are needed in process control. The YS1500 is configured upon shipment from the factory so that only the minimum required functions are available, but control functions needed for a user's specific application can be selected by setting various parameters.
Overview of YS1500 Functions
Table 1 lists some of the major functions of the YS1500 as compared with those of the earlier model, the YS150.
| Item | YS1500 | YS150 | |
|---|---|---|---|
| Input | Analog | 4 | 4 |
| Digital | 6(Dl/DO) | 1 | |
| Output | Current | 1 | 1 |
| Voltage | 2 | 2 | |
| Digital | 6(Dl/DO) | 5 | |
| Fail contact | 1 | 1 | |
| Controller mode | Single | available | available |
| Cascade | available | available | |
| Selector | available | available | |
| PID contol | PID, SAMPLE PI | PID, P | |
| Auxiliary Control Function | Input filter | available | available |
| Square root extraction for Input | available | available | |
| Ten-segment linearizer for Input | available | available | |
| Feed forward | available | available | |
| Operation mode swiching | Up to 6 can be set | 1: Function fixed | |
| Degital output definition | Up to 6 can be set | 5: Function fixed | |
| Analog output retransmission | Select PV, SV, or MV | 1: Function fixed | |
Table 1 Comparison of YS1500 and YS150 functions (new functions in red)
New Functions for the YS1500
Added functions that were previously only available with the top-of-the-line programmable indicating controller:
- Greater freedom in DI/DO assignments
A variety of status inputs/outputs can now be freely assigned to DI/DO. - Sample and hold PI control
Useful for processes with a lot of down time.
- Transmission Output function
PV, SV, and MV can now be assigned.
Setting Display

Example :Enginnering display of YS1500