Category Sitemap
Home / Our Businesses / IA / Products / Solution-based Software / Products /
AAASuite
Advanced Alarm Administrator
  1 2 3 4  
1. Automatic alarm suppression

AAASuite automatically identifies the following kinds of nuisance alarms and suppresses their repetition by the DCS functions.
   -Repeating HI/LO alarms caused by incorrect alarm setting
   -Longstanding false HI/LO alarms caused by incorrect alarm hysteresis setting
   -Oscillating HI/LO alarms caused by incorrect PID setting
   -Input out of range alarms caused by overrange
   -Input out of range alarms caused by minor transmitter problems
   -Repeating annunciators caused by incomplete the DCS sequence

2. Automatic alarm re-notification
AAASuite automatically and periodically re-notifies the following important alarms to bring them to the attentions of the operators.
   -Longstanding true HI/LO alarms
   -Longstanding input out of range alarms caused by a broken wire
3. Automatic alarm prediction
HH/LL alarms often serve as the trigger an interlock sequences that leads to an emergency shut down. AAASuite automatically predicts when a process will reach its alarm limits and issues a timely alert to operators, enabling them to intervene before a process reaches the HH/LL state.
4. Dynamic alarm setting (Optional)
An alarm threshold should be adjusted when there is a change in the operation conditions (e.g. grade change, load change). When such a change occurs, AAASuite automatically downloads the optimum alarm threshold(stored in a CSV format file) to the DCS. When the operation conditions change again, AAASuite uploads to this CSV format file current alarm threshold that is stored in the DCS.
5. Advanced and intelligent alert (Optional)
AAASuite can issue advanced types of alerts that add value in the monitoring of:
   -field instruments
   -process equipment
   -process performance
   -human error
Steps Key function Result
1 Suppression of repeating nuisance alarms Nuisance alarms drastically decreased
2 Optimization of alarm setting Nuisance alarms drastically decreased
3 Re-notification of longstanding true alarms Alerts slightly increased
4 Prediction of critical HH/LL alarms Alerts slightly increased
5 Addition of more advanced alerts Alerts slightly increased
GLOBAL  
YOKOGAWA

Powered by Ultraseek
·  AAASuite
Click here!
Top of this page