- Home>
- Our Businesses:
- Field Instruments:
- Transmitters:
- EJA Pressure/Differential Pressure Transmitters:
- EJA110A Differential Pressure Transmitter :
- EJA120A Draft Range Differential Pressure Transmitter:
- EJA130A High Static Differential Pressure Transmitter:
- EJA210A/EJA220A Flange Mounted Differential Pressure Transmitter:
- EJA310A Absolute Pressure Transmitter:
- EJA430A Gauge Pressure Transmitter:
- EJA440A High Static Gauge Pressure Transmitter:
- EJA510A/EJA530A Absolute and Gauge Pressure Transmitter:
- EJA118 Diaphragm Sealed Differential Pressure Transmitter:
- EJA438 Diaphragm Sealed Gauge Pressure Transmitter:
- EJA115 Low Flow Transmitter>
- EJA510A, EJA530A Absolute and Gauge Pressure Transmitters
EJA510A, EJA530A Absolute and Gauge Pressure Transmitters
The absolute and gauge pressure transmitter model EJA510A and EJA530A can be used to measure liquid, gas, or steam pressure.
Product Information


![]() |
| The absolute and gauge pressure transmitter model EJA510A and EJA530A can be used to measure liquid, gas, or steam pressure. Both output a 4 to 20mA DC signal corresponding to the measured pressure. |
| The EJA Series is available with BRAIN, HART, FOUNDATION™ fieldbus or PROFIBUS PA communication protocols. |
Features
| - | Excellent performance and stability |
| The EJA series uses a silicon resonant sensor formed from monocrystal silicon, a perfect material which has no hysteresis in pressure or temperature changes. The sensor minimizes overpressure, temperature change, and static pressure effects, and thus offers unmatched long-term stability. | |
| - | Compact and light-weight design |
| Half the weight of conventional models thanks to miniaturization of the casing with the amplifier ASIC, pressure cell structure, and flange. The ASIC uses the minimum number of parts and improves the reliability of the amplifier. | |
| - | Fieldbus communication capability |
| Fieldbus is a digital two-way communication system. It is a revolutionary technology for configuring instrumentation control systems and a promising successor to the standard 4 to 20 mA analog communication used in most field instruments today. EJA series offers two types of fieldbus models, FOUNDATION™ fieldbus Low Voltage Mode and PROFIBUS PA devices, which ensure interoperability between Yokogawa and other manufactures. As for software, the EJA series incorporates two AI function blocks that compute differential and static pressures to allow flexible configuration of instrumentation. |
|
Specifications
| EJA510A / EJA530A Direct Mount Type Absolute Pressure and Gauge Pressure Transmitter (Measurement values below are in absolute for EJA510A) |
|||||
| A Capsule | B Capsule | C Capsule | D Capsule | ||
| Range | 0 to 200 kPa (0 to 29 psi) |
0 to 2 MPa (0 to 290 psi) |
0 to 10 MPa (0 to 1450 psi) |
0 to 50 MPa (0 to 7200 psi) |
|
| Span | 10 to 200 kPa (1.45 to 29 psi) |
0.1 to 2 MPa (14.5 to 290 psi) |
0.5 to 10 MPa (72.5 to 1450 psi) |
5 to 50 MPa (720 to 7200 psi) |
|
| Accuracy | ±0.2% | ±0.2% | ±0.2% | ±0.2% | |
| Degrees of protection | IP67, NEMA 4X, and JIS C0920 immersion proof | ||||
| Certificates | FM, CENELEC ATEX, CSA, IECEx | ||||
| Output | 4 to 20 mA DC or FOUNDATION™ fieldbus or PROFIBUS PA 2-wire system with digital communication | ||||
| Supply voltage | BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type) Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity model and 9 to 17.5 V DC for FISCO model) |
||||
| Ambient temperature | -40 to 85 deg C (-40 to 185 deg F) (general use type) -30 to 80 deg C (-22 to 176 deg F) (with integral indicator) |
||||
| Process temperature | -40 to 120 deg C (-40 to 248 deg F) (general use type) | ||||
| Maximum overpressure | 4 MPa (580 psi) |
4 MPa (580 psi) |
20 MPa (2900 psi) |
60 MPa (8500 psi) |
|
| Mounting | Direct Mounting/2-inch pipe mounting | ||||
| Wetted parts material | Capsule | Hastelloy C-276 | |||
| Process connection |
SUS316L, Hastelloy C-276 | ||||
| Housing | Cast aluminum alloy or SUS316 equivalent stainless steel (optional) | ||||