- Home>
- Our Businesses:
- Field Instruments:
- Transmitters:
- EJX Pressure/Differential Pressure Transmitters:
- EJX110A Differential Pressure Transmitter:
- EJX120A Draft Range Differential Pressure Transmitter:
- EJX130A High Static Differential Pressure Transmitter:
- EJX210A Flange Mounted Differential Pressure Transmitter:
- EJX310A Absolute Pressure Transmitter:
- EJX430A Gauge Pressure Transmitter>
- EJX440A High Static Gauge Pressure Transmitter:
- EJX510A/EJX530A Absolute and Gauge Pressure Transmitter:
- EJX118A Diaphragm Sealed Differential Pressure Transmitter:
- EJX438A Diaphragm Sealed Gauge Pressure Transmitter:
- EJX115A Low Flow Transmitter:
- EJX910A Multivariable Transmitter:
- EJX930A Multivariable Transmitter:
- EJXMVTool™ EJX-MV Configuration DTM (FSA120):
- EJX630A/EJX610A Gauge and Absolute Pressure Transmitter:
- EJX115A Low Flow Transmitter
EJX115A Low Flow Transmitter
Product Information


![]() |
||||||||||||||||||||||||||
| The model EJX115A Low Flow Transmitter is a differential pressure transmitter assembled with an integral orifice and excellent for very low flow measurement. It outputs a 4 to 20 mA DC signal corresponding to the measured flow. The orifice is available in six types with a bore ranging from 0.508 mm to 6.350 mm. The combination of the bore selection with the differential pressure measurement span variation of the differential pressure transmitter enables a wide range of very small flow measurement. The multi-sensing technology provides the advanced diagnostic function to detect such abnormalities as an impulse line blockage or heat trace breakage. |
||||||||||||||||||||||||||
| The EJX series is available with BRAIN, HART, and FOUNDATION™ fieldbus communication protocols. | ||||||||||||||||||||||||||
|
||||||||||||||||||||||||||
Specifications
| EJX115A Low Flow Transmitter | ||||
| L Capsule | M Capsule | H Capsule | ||
| Water equivalent | 0.016 to 7.2 l/min | 0.022 to 23 l/min | 0.07 to 33 l/min | |
| Air equivalent flow | 0.44 to 198 Nl/min | 0.63 to 635 Nl/min | 2 to 910 Nl/min | |
| Differential pressure span | 1 to 10 kPa (2 to 40 inH2O) |
2 to 100 kPa (8 to 400 inH2O) |
20 to 210 kPa (80 to 840 inH2O) |
|
| Accuracy | IFO | ±5% | ±5% | ±5% |
| DP | ±0.04% | ±0.04% | ±0.04% | |
| Degrees of protection | IP67, NEMA 4X, and JIS C0920 immersion proof | |||
| Certificates | FM, CENELEC ATEX, CSA, TIIS, IECEx | |||
| Output | 4 to 20 mA DC or FOUNDATION™ fieldbus or PROFIBUS PA 2-wire system with digital communication | |||
| Supply voltage | BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type) Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity model and 9 to 17.5 V DC for FISCO model) |
|||
| Ambient temperature | -40 to 85 deg C (-40 to 185 deg F) (general use type) -30 to 80 deg C (-22 to 176 deg F) (with integral indicator) |
|||
| Process temperature | -40 to 120 deg C (-40 to 248 deg F) (general use type) | |||
| Maximum working pressure | 16 MPa (2300 psi) |
|||
| Mounting | 2-inch pipe mounting | |||
| Wetted parts material | Capsule | 316L SST (Diaphragm material is Hastelloy C-276) | ||
| Manifold | 316 SST | |||
| Cover flange | ASTM CF-8M | |||
| Housing | Cast aluminum alloy or ASTM CF-8M stainless steel (optional) | |||