- Home>
- Our Businesses:
- Field Instruments:
- Transmitters:
- EJX Pressure/Differential Pressure Transmitters:
- EJX110A Differential Pressure Transmitter:
- EJX120A Draft Range Differential Pressure Transmitter:
- EJX130A High Static Differential Pressure Transmitter:
- EJX210A Flange Mounted Differential Pressure Transmitter:
- EJX310A Absolute Pressure Transmitter:
- EJX430A Gauge Pressure Transmitter>
- EJX440A High Static Gauge Pressure Transmitter:
- EJX510A/EJX530A Absolute and Gauge Pressure Transmitter:
- EJX118A Diaphragm Sealed Differential Pressure Transmitter:
- EJX438A Diaphragm Sealed Gauge Pressure Transmitter:
- EJX115A Low Flow Transmitter:
- EJX910A Multivariable Transmitter:
- EJX930A Multivariable Transmitter:
- EJXMVTool™ EJX-MV Configuration DTM (FSA120):
- EJX630A/EJX610A Gauge and Absolute Pressure Transmitter:
- EJX210A Flange Mounted Differential Pressure Transmitter
Multi-sensing, an Evolution in the Silicon Resonant Sensor
EJX210A Flange Mounted Differential Pressure Transmitter
Product Information


![]() |
| The high performance flange mounted differential pressure transmitter EJX210A can be used to measure levels of densities of solidifying or precipitating liquids. The multi-sensing technology provides the advanced diagnostic function to detect such abnormalities as an impulse line blockage. |
| The EJX series is available with BRAIN, HART, and FOUNDATION™ fieldbus communication protocols. |
Specifications
| EJX210A Flange Mounted Differential Pressure Transmitter | ||
| M Capsule | H Capsule | |
| Range | -100 to 100 kPa (-400 to 400 inH2O) |
-500 to 500 kPa (-2000 to 2000 inH2O) |
| Span | 1 to 100 kPa (4 to 400 inH2O) |
5 to 500 kPa (20 to 2000 inH2O) |
| Accuracy | ±0.075% | ±0.075% |
| Degrees of protection | IP67, NEMA 4X, and JIS C0920 immersion proof | |
| Certificates | FM, CENELEC ATEX, CSA, IECEx | |
| Output | 4 to 20 mA DC or FOUNDATION™ fieldbus, 2-wire system with digital communication | |
| Supply voltage | BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type) Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity and 9 to 17.5 V DC for FISCO) |
|
| Ambient temperature | -40 to 85 deg C (-40 to 185 deg F) (general use type) -10 to 85 deg C (14 to 185 deg F) (high temperature use type) -30 to 80 deg C (-22 to 176 deg F) (with integral indicator) |
|
| Process temperature | -40 to 120 deg C (-40 to 248 deg F) (general use type) -10 to 250 deg C (14 to 482 deg F) (high temperature use type) |
|
| Maximum working pressure | Flange rating pressure | |
| Mounting | Flange mounting | |
| Process flange size | Flush type: 3-inch (80 mm),2-inch (50 mm),1 1/2-inch (40 mm) Extended type: 4-inch (100 mm), 3-inch (80 mm) |
|
| Diaphragm material (High side) |
SUS316L, Hastelloy C-276, Tantalum | |
| Process flange material | S25C, SUS304, SUS316 | |
| Housing | Cast aluminum alloy or ASTM CF-8M stainless steel (optional) | |