Multi-sensing, an Evolution in the Silicon Resonant Sensor

EJX430A Gauge Pressure Transmitter

Product Information

EJX430A Gauge Pressure Transmitter

BRAIN HART FF TUV CE Ctick Logo

EJX Series Differential Pressure Transmitter logo
The high performance gauge pressure transmitter EJX430A features single crystal silicon resonant sensor and is suitable to measure liquid, gas, or steam pressure.
The multi-sensing technology provides the advanced diagnostic function to detect such abnormalities as an impulse line blockage or heat trace breakage.
 
The EJX series is available with BRAIN, HART, and FOUNDATION™ fieldbus communication protocols.
 
 
  EJX430A general specifications PDF
 
  EJX430A Reference Class PDF
 
  EJX430A User's Manual PDF
Terms of Use for Manuals
 
  List of EJX series gauge pressure transmitter general specifications
 
  List of EJX series gauge pressure transmitter drawings
 

Specifications

  EJX430A Gauge Pressure Transmitter
H Capsule A Capsule B Capsule
Range -400 to 2000 inH2O -14.5 to 500 psi -14.5 to 2300 psi
Span 10 to 2000 inH2O 2.5 to 500 psi 12 to 2300 psi
Accuracy ±0.04% ±0.04% ±0.04%
Accuracy  (Note * Below) ±0.025% * ±0.025% * ±0.025% *
Degrees of protection IP67, NEMA 4X, and JIS C0920 immersion proof
Certificates FM, CENELEC ATEX, CSA, IECEx
Output 4 to 20 mA DC or FOUNDATION™ fieldbus, 2-wire system with digital communication
Supply voltage BRAIN and HART:10.5 to 42 V DC
(10.5 to 30 V DC for Intrinsically safe type)
Fieldbus:9 to 32 V DC
(9 to 24 V DC for Entity and 9 to 17.5 V DC for FISCO)
Ambient temperature -40 to 85 deg C (-40 to 185 deg F) (general use type)
-30 to 80 deg C (-22 to 176 deg F) (with integral indicator)
Process temperature -40 to 120 deg C (-40 to 248 deg F) (general use type)
Maximum overpressure 16 MPa (2300 psig) 25 MPa (3600 psig)
Mounting 2-inch pipe mounting
Wetted parts material Capsule 316L SST(Diaphragm material is Hastelloy C-276),
Hastelloy C-276,Tantalum,Monel
Cover flange ASTM CF-8M,Hastelloy C-276,Monel
Housing Cast aluminum alloy or ASTM CF-8M stainless steel (option)
* Certain Conditions apply refer to GS for more information

Get Adobe Reader®Viewing pdf files requires Adobe Reader