Why Purge Gas and How Much is Typically Consumed on my TDLS8000?

Video FAQ

Questions

  • Why purge gas on a TDLS8000?
  • How much purge gas is typically consumed on a TDLS8000?
  • Why purge gas and how much is typically consumed on a TDLS8000?

Answers

  1. 4 Purge Lines: 2 for the electronics (flow 1-5 std liters per min), 2 for windows (flow 25-55 std liters per min).
  2. A total of 50-120 standard liters per min flow rate is application dependent. Dirty or hotter process will require more flow
  3. The TDLS8000 is non-incendive and does not require a purge to maintain hazardous ratings. The purge gas is required to keep the electronics and process windows cool, clean, and dry. Average consumption can run between 50-120 standard liters per min.

For immediate assistance or to ask your own question, please use the chatbox to the right, contact us at support@us.yokogawa.com, or 1.800.888.6400

Related Products & Solutions

  • In-Situ Gas Analyzer TDLS8000

    Yokogawa’s new TDLS8000 houses all of the industry’s leading features in one robust device. The platform design is for in situ measurements which negates the need for sample extraction and conditioning.

    See More

Top