Question
Common Items
Model MY40 Digital Insulation Testers
Model MY10 Analog Insulation Testers
Model 3213A Analog Insulation Testers
Model 3235 Earth Tester
Answer
Common Items
The ratings of 25, 50 and 125V are applicable to instruments released after the revisions to JIS C1302-1994.
Top of this page
IS C1302: 2002 clause 3.1.7 is summarized in the table below. The 1st effective measuring range has a tolerance of ±5% of reading, while the second effective measuring range has a tolerance of ±10% of reading. Effective measuring range means the measuring range where its intrinsic error is guaranteed. Table below explains the details.

Rating 1st Effective Measuring Range 2nd Effective Measuring Range Central Scale Marking
100V/20MΩ 0.02 to 10MΩ 10 to 20MΩ 0.5MΩ
250V/50MΩ 0.05 to 20MΩ 20 to 50MΩ 1MΩ
500V/100MΩ 0.1 to 50MΩ 50 to 100MΩ 2MΩ
500V/1000MΩ 1 to 500MΩ 500 to 1000MΩ 20MΩ
1000V/2000MΩ 2 to 1000MΩ 1000 to 2000MΩ 50MΩ
Top of this page
DC voltage to be impressed is generated in the resistance insulation testers and apply the same.
Top of this page
Insulation testers are not used for live lines. The measurement of live lines requires Yokogawa Model 30031A Leakage Clamp-on Tester which measures the current leakages.
It estimates the insulation resistance value equivalently.
Top of this page
The following pre-calibrated equipment shall be required.
* Yokogawa Model 279303 Decade Resistance Box.
* Yokogawa Model 394790 Calibration Box for Resistance Insulation Tester.
* Yokogawa Model 270800 Galvanometer.
* Any DC voltage standard which generates DC 1300V.

Unless otherwise specified, the testing for insulation testers shall be performed in the following conditions.
・Ambient Temperature: 23℃±5℃
・Relative Humidity: 45 to 75%
・Position: Vertical (angle of gradient is less than 5°from vertical level)
・External Magnetic Field: None (least effect direction against magnetic field of earth)
・Battery Voltage: Battery effective range
Top of this page
It depends on the product. Some models can use and some cannot. The MY40 Digital Insulation Tester and MY10 Analog Insulation Tester have a battery checking function that enables the use of rechargeable batteries.
Top of this page
People tend to think that the LINE is + polar. Actually, however, the EARTH is + polar and generates higher potentials.
Top of this page
There are two (2) kinds of terminals available for insulation testers, one is line terminal L (LINE) . and the other is grounding terminal E (EARTH). This terminal L is stipulated to connect to "- polar side" of DC power supply (high pressure generating circuit) through the indication circuit which is located in the inside of insulation tester and terminal E is to "+ polar side" of DC power supply.

In general, DC grounding insulation measurement for the object to be measured is as follows. Compare the two ways of measurements, grounding side of the object to be measured is connected to terminal L, and non-grounding side to terminal E, the former outputs the smaller insulation resistance value. It is assumed that the fiber of the insulating material such as insulation paper or cotton contains much moisture, the insulation resistance value changes in accordance with the polarity changes of DC power supply. Therefore, transposing line probe and earth probe of the insulation tester may change the measuring value measuring range depending on the object to be measured.

The reasons why the earth probe is connected to the grounding side of the object to be measured are as follows.
* Insulation resistance value may vary in accordance with the terminal
   E connection either to grounding or non-grounding side.
* It is easier to detect the insulation failure.
* Safety in use is considered.

Accordingly, connect the terminal E to grounding side of the object to be measured, and the terminal L to non-grounding side. Terminals for insulation testers are line terminal (LINE) and grounding terminal (EARTH).
Top of this page
Descriptions in the catalogs and other sales literatures have been made based on JIS standards. Therefore, the term of "accuracy" which is generally used in the test and measuring instruments is not used for resistance measurements, but specified as "tolerance" instead. The term "rdg" means the value indicated by the instrument, and ±5% of rdg means there is allowable error of ±5% of the value displayed.
Top of this page
Model MY40 Digital Insulation Testers
It is possible to allocate as many as three (3) user-defined reference values to each rating.
Top of this page
Nominated storage temperature is -10 to 60℃ and humidity is less than 70% RH. In addition, the batteries should be removed and free from condensation for storing.
Top of this page
Working temperature of 0 to 40℃ and humidity of 90% RH maximum are preferable.
In addition, please do not use the products under condensed conditions.
Top of this page
Model MY10 Analog Insulation Testers
Part # 9108XA accessory housing case holds the line probe (98001) and the earth probe (98002) only. While, the Model 93015 Carrying Case holds the MY10 main unit, line probe and earth probe. Please note that the Model MY10 main unit should be put in the case with the yellow cover removed.
Top of this page
Model 3213A Analog Insulation Testers
It is normal. Since the revisions of JIS C1302 in 1994, non-loaded (open circuit) voltage should not exceed 130% of rated measuring voltage.
Where, the equation is 500V x 130% = 650V. Therefore, the calculated value of approx.
640V could be understood to be normal.
Top of this page
First effective measuring range for this unit is 2MΩ~1000MΩand second effective measuring ranges are 1MΩ~2MΩ and 1000MΩ~2000MΩ. In addition, zero indication and infinite indication mean that 0 (zero) and ∞(infinite) scale positions allow less than 0.7% of scale length as a tolerance.
Top of this page
The voltage output is measured in a null method by connecting Yokogawa Model 270800 Galvanometer between the DC voltage generator which generates DC 1300V and measuring terminal. Confirmation of nominal current of 1mA is available by connecting 500kΩ(= rated voltage/1mA = 500V/1mA) to an ammeter in series. Summaries of JIS C1302: 2002 are as follows.

Unless otherwise specified, the testing for insulation testers shall be performed in the following conditions.
・Ambient Temperature: 23℃±5℃
・Relative Humidity: 45 to 75%
・Position: Vertical (angle of gradient is less than 5°from vertical level)
・External Magnetic Field: None (least effect direction against magnetic field of earth)
・Battery Voltage: Battery effective range

* Open circuit voltage test
Measuring terminal test at infinite scaleTest is performed by connecting the voltmeter (current consumption is less than 10 μA) between grounding terminal and guard terminal. Please use voltage divider whenever it is required. Tolerance should not exceed 1.3 times of rated measuring voltage.

* Rated measuring current test
Test is performed by connecting the resistance below and DC ammeter (internal resistance should be less than 200Ω) in series between measuring terminals. Please check if the reading current are within the following tolerance.

Model Rated value Resistance (test point) Tolerance
321341 100V/20MΩ 0.1MΩ 1.0 to 1.2mA
321342 250V/50MΩ 0.25MΩ 1.0 to 1.2mA
321343 500V/100MΩ 0.5MΩ 1.0 to 1.2mA
321344 500V/1000MΩ 0.5MΩ 1.0 to 1.2mA
321345 1000V/2000MΩ 1MΩ 1.0 to 1.2mA
Top of this page
Model 3235 Earth Tester
Cause short circuit between the terminals P - C, and apply known resistance (10Ω, 100Ωor so) between the terminals P - E. It is adequate to check the operation to know the results being within the tolerance by rotating the dial just like the grounding resistance measurements.
For simple calibration, connect Rp = Rc = 500Ω and apply known resistance (0, 2, 10, 20, 100, 200, 300, 1000Ω) to Re and confirm if the checking results are within the tolerance by rotating the dial just like the grounding resistance measurements.
Top of this page

Release of 2558A

2558A
2558A AC Voltage Current Standard New!

Details

Release of WT300 Series

WT300 Series
WT300 Series Digital Power Meters New!

Details

Release of DLM4000

DLM4000
DLM4000 series Mixed Signal Oscilloscope New!

Details

Release of CL420

CL420
Clamp-on Process Meter for DC mA Current #CL420 New!

Details

Release of WT1800

WT1800
WT1800 Precision Power Analyzer

Details

Release of DL850/DL850V

DL850/DL850V
DL850/DL850V Scopecorder

Details

Release of AQ6370C

AQ6370C
AQ6370C Optical Spectrum Analyzer

Details