YS1310

The YS1310 Indicator with Alarms is an input indicator that has alarms with two inputs. Two loops can be displayed simultaneously. A high limit alarm, low limit alarm, high-high limit alarm, and low-low limit alarm can be generated for each of the two inputs, and the AND connection or OR connection of arbitrary alarms can be output from a total of 6 contacts. The YS1310 offers high reliability thanks to Yokogawa's proprietary technology, user friendliness, and expandability. The basic type conforming to the DIN short case size contributes to space saving for mounting, and complies with standards (CE and FM). For easy replacement of earlier models requiring the same panel cutout dimensions and depth as those of earlier models are also offered.

Details

Features

  • A full-dot color LCD Clear visibility of the display screen is ensured even in direct sunlight in the early morning and late afternoon. The user can freely access a desired operation screen from meter, trend, bar graph, alarm, and event displays. All parameters can be set via the front panel display.
  • The parameters can all be set by operation on the front panel (no need to draw out the internal unit).
  • Parameters can also be set using YSS1000 Setting Software available separately.
  • Can be driven by either an AC (100 V) or DC (24 V) power supply. (Must be specified upon ordering if using a 220–240 V DC power supply.)
  • Dust- and splash-proof IP54 faceplate (for basic type only)
  • Depth 250 mm (only for the basic type)
  • No battery or capacitor is used for memory backup. No maintenance is required because batteries and backup capacitors are not used.
  • CE mark (for basic types and YS100-compatible type only)
  • FM non-incentive explosion protection (option, for basic types only) (Under an application)
  • Communication (option) Ethernet (Modbus/TCP) (for basic types only) RS485 (PC Link, Modbus, YS protocol, unavailable for YS80 internal unit-compatible type)
  • Compatibility with the YS100 series Setting and control operations can be done with the same feel. In the case of the basic type, terminal-to-terminal pitches differ but the signal-to-terminal arrangement is almost the same. The following functions are included to ensure compatibility with the SIHK.
  • Meter Display was added to the Operation Display.
  • Housing for replacement purposes (SHUP-000 separately available)

Easy to use

Display

 

Programming
YSS1000 Configuration and Programming Software

Programming demonstration video

Programming demonstration video 

Three connection modes

Three connection modes
Connection modes: USB, Ethernet or RS485
When connecting via RS485 or Ethernet, a communication option is required on the main unit.

Full set of computation functions

  • Supports parameter setting for all YS1000 models

Password protection function

Passwords can be assigned to user programs to prevent unauthorized access to proprietary programs.
A password on the main unit prevents unexpected changes in the engineering parameters.

Compact case
Designed with a Lightweight, Compact Case

Designed with a Lightweight, Compact Case

Designed with a Lightweight, Compact Case

Provides for greater freedom of instrumentation design

Compact, lightweight design allows the use of smaller and less expensive panel. Moreover, it allows attachment to doors which was previously difficult.

Simple exterior 

High reliability

Battery free memory backup

Nonvolatile memory is used for memory backup. Service life is improved because no batteries, backup capacitors, or other components are used.

 

AC/DC power supply resists powerline fluctuations

The AC/DC (100 V /24 V ) power supply powers the instrument to provide consistent performance.Also accepts DC power regardless of polarity (specify 220 V power supply when ordering).

 

Improved basic control performance

The YS1000 series achieves higher performance than previous models (YS100 series).

  • I/O accuracy
    Voltage input accuracy: ±0.2% ⇒ ±0.1%
    Voltage output accuracy: ±0.3% ⇒ ±0.1%
    Current output accuracy: ±1.0% ⇒ ±0.2%
  • Internal data resolution of the I/O signal: 1/1000 ⇒ 1/10000
  • Internal computation resolution of PID and other computations: 1/4096 ⇒ 1/65536

 

Front panel conforms to the IP54 waterproof standard

Tougher environmental resistance.

Front panel conforms to the IP54 waterproof standard

 

Other specification

  • CE Mark (for basic type and compatible type for YS100)
  • FM nonincendive approved (FM Class I, DIV 2)
  • CSA safety and nonincendive approved (Class I, DIV 2)

Powerful and Flexible

Ethernet support

The instrument can be easily connected to DAQWORX, SMARTDAC+, general-purpose SCADA, and OPC servers via Ethernet (Modbus/TCP).

Ethernet support

Ethernet : Available to the YS1000 basic type. Modbus/TCP server function (one connection).


Communication with PLC

Connections are enabled using the FA-M3' s UT link module and the RS485 communication function. No programming is necessary to exchange data between the instrument and the FA-M3.

Communication with PLC

The YS1000 can also be connected to PLCs of various manufacturers via the Modbus communication protocol.
 

Communication with CENTUM

As with previous models, communication with Yokogawa's DCS (CENTUM) is supported. This is ideal for DCS backup in chemical plants and other applications requiring extreamly high reliability.

Applicable Models: YS1700,YS1500,YS1350,and YS1360

Communication with CENTUM

Compatibility 

Zdroje

Přehled:

Best Solution for Automatic Boiler Control
Sensors and controllers for the efficiency and environmental performance

Průmysly:
Přehled:

For safe and efficient operation, the quality of feedwater, steam, and condensate in boiler plants must be controlled and maintained in the most favorable conditions.

Přehled:

Floating-point format calculations have enabled physical quantities (in engineering units) to be used in calculations.

Přehled:

To technology in iron & steel industry is continuously improved to obtain the best possible performance. The improved plant performance gives rise to the higher quality improvement and lower cost, and simultaneously environmental friendly plant operation.

Průmysly:
Přehled:

Continuous technology improvement is ongoing in the pulp & paper industry to obtain the best possible performance. The improved plant performance translates to the higher quality improvement and lower cost, and simultaneously environmental friendly plant operation.

Průmysly:
Přehled:

Automated control of industrial boilers is an excellent application for YS1700 microprocessor-based loop controllers. These instruments can be programmed to perform the operations of plant master, boiler master, fuel and air control with oxygen trim and drum level/feedwater control.

When using a 24 VDC power supply, since the rated power specification is 3 W, use the YS021 (250 Ω shunt resistor). For others, you can use the X010-250-1 external precision resistor with a rated power of 0.5 W.
If you share (wire) the DI's COM there will be no isolation between the DI's inputs, but otherwise there should be no problem.
Refer to the following materials with replacement model formats, installation and wiring, and outer dimensions. TI 01B08A02-05EN YS1000 Replacement Guide Overview, Model Conversion TI 01B08A02-06EN YS1000 Series Replacement Guide Installation and...