UT450 Digital Indicating Controller
Hinweis: Dieses Produkt wurde eingestellt am Sehen Sie sich dieses Ersatzprodukt an:

Publikationen

Yes. Use 1SP, 2SP, 4SP, and 8SP.
This happens when SP tracking is turned ON in the setup parameters. Turn this parameter (SPT) OFF.
Can I control chemical dosing?
(ns-faq-green-9023-spec)
The auxiliary analog input function supports this with a ratio bias function.
This is supported on UTAdvanded series UT52A / UT55A / UT75A / UP55A.
Yes, by setting RET=3(OUT). (Note that this is position proportional only.)
This function supplies power to 2-wire transmitters. It differs depending on the specifications of the transmitter, but the input accepts 100 Ω resistors. 100 Ω resistor (model: X010-100-2, sold seperately)
When switching with contacts, communication cannot be used.
Yes. The selection in the OT=0 to 3 setting in the setup parameters will be 1 output.
This is a function in which output occurs a specified time after an alarm set point is exceeded. If you clear the alarm point during operation of the timer, the timer is reset.
With a UP program controller or UT digital indicating controller as the parent station and multiple UT digital indicating controllers as the child stations, the children perform the same actions that are carried out on the parent. ...
Once input is set, IN is not displayed when you turn the power ON.
Even when you expand the applicable range of the PID constant, the process states fluctuate, or response is unstable and hunting occurs (control responses fluctuate), this function is effective for stabilizing control and suppressing hunting. Normall...
This is a protocol for communication with general purpose PCs and graphic panels, and also the FA-M3: You can communicate with Yokogawa PLC range free controller UT link modules and serial communication modules. Also, you can easily connect with PLCs...
This is an overshoot suppression function that uses fuzzy logic. It constantly monitors deviation, and if it detects the possibility of an overshoot, it automatically changes the set point to a somewhat lower temp value (sub set point SSP). When y...
Ladder communication is a protocol for communication with PLCs. Aside from Yokogawa PLCs, you can communicate with Mitsubishi MELSEC-Q/A series calculator link units (using A1SJ71UC24-R4 or A1SJ71C24-R4). ...
This is a protocol for communication with general purpose PCs and graphic panels. The UT130/UT150 can communicate with standard PCs. ...
The DO206 items are used when in cascade control mode. For other modes, use DO201.
Set the following: P=100, I=D=OFF, DR=DIR (direct action), MR=0, SP=0.
I can't switch the SP.
(ns-faq-green-9053-spec)
Check whether you are trying to switch it via communication, or whether it is the zone PID.
Yes, if it is a heating/cooling type.
Why don't PID items appear?
(ns-faq-green-9044-spec)
They don't appear with OT=3 ON/OFF control.
There is no control output.
(ns-faq-green-9085-spec)
Check whether MAN operation (manual) is selected for the output.
Check whether you can output manually. If not, check wether OL (cooling output limiter)=100%.
What are the PID switching methods?
(ns-faq-green-9041-spec)
There is a zone, contact, and parameter switching method.
Output stops when the status is STOP.
(ns-faq-green-9031-spec)
When RET=1 or 2, the STOP has no effect.
With the UT300 series, only use 1PID. With UT400/500/700 models, the PID used just prior to switching to remote input is used. When using SP switching during remote input, only the PID switches.
Can I perform CC-Link communication?
(ns-faq-green-9035-connect)
Yes, by using the UTAdvanced series.
DO215, used for communication, is not backed up.
How many PID groups can be used?
(ns-faq-green-9040-spec)
4 groups for the UT300 series, and 8 groups for the UT400/500/700 series.
These are used when 2-wire transmitters are used in the field. They provide cost savings since they do not need to be purchased separately. 24 V (21.6–28.0 VDC, 30 mA MAX) sensor power supplies can be specified with the following models: UT551,...
The UT300/400/500/700 series, and the UP350/351/550/750. However, the LL200 custom computation function is only compatible with the UT750/UP750.
Set them in the order, Alarm type → Alarm setting values. They will also not be displayed if you select an alarm for which no value is set.
The are set with a real number. For temperature, it is set in degrees Celsius.
If you set + dead zone in the settings, you can get an area where no outputs occur. If you set - dead zone, you can get an area where both outputs occur at the same time.
Set both item P on the heating side and item Pc on the cooling side to 0.0.
It depends on the model. The following lists the readable registers by model. UT100 series: D0001–D0009 UT300 series: D0001–D0008 UT400/UT500/UT700 series: D0001–D0025 UP350: D0001–D0008 UP550/UP750: D0001–D0025 ...
Check that the operating parameters UPR and DNR are both OFF.
No. When an alarm occurs, it automatically recovers if values enter the normal range.
Check whether the wiring to the power supply terminal is correct. If only the LCD on the UT/UP700 does not display, a custom computation may be set for no display. If the PV display is also blank, this may indicate product failure. Please contact you...
The output is 0% if there is a hardware failure such as an internal microprocessor.
PCBs (polychlorinated biphenyl) were banned from manufacturing and imports in 1975. The GREEN series began to be manufactured in 1997, and do not include PCBs.
The PV value can be written by using the ladder sequence function of UTAdvanced series. However, when communication is interrupted, the PV value is retained.
There are 2 types of output available, FAIL and "failure diagnosis."
The sensor wire on the input side might be broken or disconnected.
What are energize/de-energize alarms?
(ns-faq-green-9076-term)
For energize alarms, ON contact results when an alarm occurs. For de-energize alarms, OFF contact results when an alarm occurs. Note that OFF contact also results when the power fails.
Do Green series controllers support Ethernet?
(ns-faq-green-9009-connect)
Yes. This requires an RS-485/Ethernet converter such as VJET. The controller must also have a communication option. Some models can be connected directly with the UTAdvanced series.
There is no current input range.
(ns-faq-green-9018-spec)
Use a resistor to input current as voltage. A resistor is available: X010-250-2 (250 Ω).
This is a limit on the number of times you can write to the element used (EEP-ROM).
What are direct and reverse action?
(ns-faq-green-9017-term)
Generally, reverse action means heating control and direct action means cooling control. When output is reverse action, output is ON during PVSP.
These cannot be set when in Custom Computation mode.
How do I change the input type?
(ns-faq-green-9014-spec)
If you change the input type, parameters will be initialized. We do not recommend that you make changes while in operation.
Yes, but if you change some parameters, others will be initialized. We do not recommend that you make changes while in operation.
600 Ω.
Yes, MELSEC-A, MELSEC-Q, and MELSEC-FX.
If the operation mode is STOP or MAN, they are not displayed.
Ladder communication is used when communicating with the Computer link unit/Serial communication unit. Modbus/RTU is used for communication with the Modbus communication module.
Yes, the Auto tuning function.
Sample programs and dedicated communication materials are available for MELSEC-A/MELSEC-Q.
Almost all items can be accessed, including PV reading, SP writing, and PID setting.
You can use the conversion tool. You don’t have to do anything after you create it. The steps are as follows: Perform the Green conversion using the conversion tool. Write the converted file to the UTA (with the CC-Link option) main unit. ...
Yes. Software for converting your existing controller parameter data for use with the UTAdvanced series is available for download free of charge. GREEN to UTAdvanced Conversion Tool *Log-in Required ...
The common for all GREEN series alarm relay outputs are shared. In the UTAdvanced series, each alarm relay output has its own common. If used the same way, use external wiring to connect common to common.
Program changes for reading PV and OUT, writing SP, and other basic parameters are not necessary. There are registers and relays that support the GREEN series. For details see the UTAdvanced series communication interface (RS-485, Ethernet) user'...

Downloads

Möchten Sie weitere Informationen über unsere Mitarbeiter, Technologien und Lösungen?

Kontakt

Top