Integration of Real-time Utility Monitoring with a DCS

다운로드 (912 KB)

Introduction

Photo 1

The discharge of improperly treated industrial chemicals and fuel gas can have a major impact on the environment, posing a serious threat to public health. Concurrent with the global growth of manufacturing operations to keep pace with market trends, many countries are taking measures to deal with environmental problems. In Japan, for instance, the Air Pollution Control Law and the Water Pollution Control Law require businesses to control toxic emissions. Both are revised periodically. To comply with government regulations and fulfill their responsibilities to society, businesses are upgrading their monitoring and control of waste treatment utilities, including waste water treatment and dust filtering facilities.

Effluent control in Japan

Closed bodies of water such as lakes, inland seas, and bays where there is relatively little inflow or outflow are particularly vulnerable to water pollution. Eutrophication caused by organic pollution can lead to problems such as massive plankton outbreaks and red tides. With the implementation in 2001 of the fifth stage of the Japanese Total Pollutant Load Control Program, chemical oxygen demand (COD) restrictions were enhanced. In addition, nitrogen and phosphorus were added to the list of controlled substances as they are believed to be a cause of red tides.

Air pollution control in Japan

Respiratory function can be affected by suspended particulate matter. Volatile organic compounds (VOC), which were once widely used as cleaning agents in the manufacturing of semiconductors and other electric and electronic devices, are thought to play a role in generating photochemical oxidants. The Japanese government placed restrictions on VOC in 2004 when it revised the Air Pollution Control Law.

 

Expected Benefits

Industrial Effluents

The waste treatment facilities and main plants integration, achieved with the new "Integrated Operation" system architecture, contributes toward the reduction of factory related pollution with following benefits:

Blind spots eliminated

When utility data is displayed on multiple instruments and/or recorders, blind spots can occur in utility monitoring. By bringing together this utility data in the STARDOM FCN/FCJ hybrid PLCs, this data together with other plant status information can be monitored and manipulated from the DCS HMI. This eliminates blind spots.

Reduced risk of uncontrolled discharge of industrial effluents

From the central control room, which is manned around the clock, personnel operate and control the whole plant from the Distributed Control System (DCS) Human Machine Interface (HMI). By integrating into the DCS HMI the data and alarms from utilities, which are often monitored independently, the probability of an uncontrolled discharge of industrial effluents into a river is dramatically reduced. This also makes it possible to reduce the frequency of on-site patrols.

Agile action to the frequent utility revamps

In a new plant, the utility data can be integrated in the DCS HMI. Whenever utilities are revamped, the hybrid PLC logic needs to be modified. Although these changes can affect the operation of the DCS controllers, which handle the main process, no changes are made to the DCS logic. Modifying the DCS logic is not the solution to this problem. With an integrated operation architecture, the DCS logic does not need to be modified. The hybrid PLC data that has been modified as a result of the utility revamps can be accessed by the DCS via the System Integration OPC Station (SIOS). This enables the hybrid PLC data to be handled in the same way as the data from the DCS function blocks.

Reduced capital expenditure (CAPEX) for utility revamps

Each time utilities are revamped, rewiring and re-engineering of the DCS controllers is required. This new architecture eliminates the need to rewire the DCS controller and modify its logic, reducing the overall cost of a utility revamp. This is made possible by the SIOS, which allows the hybrid PLC function ownership due to longer sensor prove life-time.

Reduced training time

Every time a new system is installed, personnel must undergo training to learn how to operate it. With the integrated operation architecture, this is not necessary because there is no change in how the data and alarms from the FCN/JCJ hybrid PLCs are handled from the DCS HMI. Also, the automatically generated FCN/FCJ tuning windows have the same look and feel as the DCS tuning windows.

 

Process Description

Monitoring and Control Systems for Waste Treatment Utility

Monitoring and control systems for waste treatment utility

For waste treatment facilities to comply with stricter regulations and operate safely and efficiently, monitoring and control systems with the following characteristics are required:

  • Can flexibly accommodate regulatory changes in monitoring subjects and limit values
  • Monitoring and control points can be easily added at each process step
  • The monitoring and control system can cope in real time with emergencies such as the discharge of toxic effluents into a river in a remote location.
  • Seamlessly integrates with a centralized monitoring and control system, enabling integration of utility and production processes
  • Can operate with high reliability and stability for long periods of time
 

Challenge of Conventional Monitoring and Control Systems

Existing waste treatment utilities employ the following systems, depending on the facility scale and the treatment complexity.

On-site monitoring

Operation and monitoring with on-site instruments

Instruments are installed on-site. Single-loop controllers and the like perform control as well as operation and monitoring functions, and data are stored on recorders. This system is employed with utilities located in remote locations, and requires regular site patrols.

  • Relying chiefly on periodic on-site patrols does not allow real-time responses to emergency alarms.
  • The inability to operate in real time makes it difficult to control the utility if the emergency level is raised.
  • Readings are displayed on multiple instruments or panels, making oversights more likely.
  • Data displayed on different panels cannot be integrated at a central location.

Control through PLC and operation and monitoring with on-site displays

The system is located far from the main plant and thus performs control and monitoring independently. On-site personnel or periodic patrols are available.

  • When unattended, the system cannot respond to emergency alarms in real time.
  • When there are multiple utilities, their statuses cannot be centrally controlled.
  • Integrated management of the main and utility processes is not possible.

Centralized monitoring

Control through PLC and operation and monitoring on a DCS via data integration using Modbus or other method

Control is localized within the utility and only important data are collected and monitored from the centralized monitoring and control system.

  • To comply with stricter regulations and accommodate data from an increased number of monitoring points, the DCS controller logic needs to be modified.

Control, monitoring, and operation all performed on a DCS using remote I/O

Measurements for all monitoring points are input to the DCS. As both monitoring and control are performed the centralized system, the operator can make real-time responses to changes in the utility status.

  • Changes to monitoring points and the utility's control logic require modification of the DCS logic.
  • Control of both main and utility processes requires more complex DCS logic.
  • The utility logic places a heavy demand on DCS resources CPU and I/O points.
 

Solution

System ConfigurationThe Yokogawa solution: Integrated operation

Same look and feel operation and monitoring on the DCS HMI

To overcome the limitations of conventional utility systems, Yokogawa proposes a new utility monitoring and control system architecture that seamlessly integrates hybrid PLCs with the DCS. The new system architecture can flexibly accommodate changes made to improve the operational efficiency of utilities.

Via a system integration OPC station (SIOS), the function blocks of the hybrid PLCs (FCN/FCJ controllers) can be operated and monitored from the DCS human-machine interface (HMI), and the display of data from both systems has the same look and feel. And with the Consolidated Alarm Management System for HIS (CAMS for HIS), all alarm management is integrated. Both the data and the alarms from the FCN/FCJ are integrated into the DCS HMI.

No change to the DCS system architecture

The monitoring and control of utilities by the FCN/FCJ controllers can be integrated into the DCS without having to change the DCS system logic or architecture. This is because the data from the FCN/FCJ hybrid PLCs passes through the SIOS, enabling it to be handled in the same way as the data from the DCS function blocks.

Automatic creation of tuning windows

Tuning windows for the hybrid PLC function blocks are automatically created in the DCS HMI. Specially adapted tuning windows for these function blocks are not required. 

Conclusion

There is an increasing need for a DCS with the ultra-high reliability required by plants. At the same time, the ability to raise productivity by flexibly improving and expanding subsidiary facilities and utilities is required. Distributing the facility and utility monitoring and control logic among the hybrid PLCs facilitates plant expansion and improvement, but with a conventional distributed system the DCS logic must be modified.

Yokogawa proposes SIOS-based integrated operation for the same look & feel display of hybrid PLC function blocks on the DCS HMI. The ability to access the hybrid PLC function blocks in the DCS HMI makes possible the automatic generation of tuning windows and trend windows, substantially improving engineering efficiency. Through the seamless integration of independent utilities in a centralized monitoring and control system, an entire plant can be monitored and operated in real time from the DCS HMI, increasing the utilities' efficiency and operational safety.

업종

  • 광업 및 금속

    채광 작업을 통해 지구로부터 귀중한 광물 또는 지질 물질(geological materials)을 얻을 수 있습니다. 경쟁적인 회수를 위해 적은 운영비 및 엄격한 안전 및 환경 규제로 높은 처리량과 높은 프로세스 가용성이 요구되고 있습니다.

    See More
  • 수처리

    Yokogawa는 수처리 설비의 더욱 안정적인 운영을 위한 최적의 솔루션을 제공합니다. 이러한 솔루션에는 정교한 기술, 탁월한 제품 품질 및 라이프 사이클 전반에 걸친 광범위한 애플리케이션 노하우가 포함됩니다.

    See More
  • 식음료

    Yokogawa는 오늘날의 식음료 기업들이 기후 변화, 소비자 수요 및 글로벌 경쟁력 향상이라는 전례 없는 도전에 직면해 있다는 것을 알고 있습니다. 이러한 도전을 극복하기 위해서는 생산, 자산 관리, 식품 안전 및 품질이라는 핵심 분야에 초점을 맞춘 혁신적인 솔루션이 필요합니다.

    See More
  • 의약품

    제약 산업은 현재 대형 신흥 시장에서 발생되는 기회를 최대한 활용하는 것이 중요한 과제에 직면해 있습니다. 이에 그 어느 때보다 제약 회사들은 수익성을 향상시킬 린 제조 기술을 도입해야 합니다. 세계 최고의 산업 자동화 공급업체 중 하나인 Yokogawa는 귀사의 모범 제조 수행에 맞는 최고의 솔루션을 제공하기 위해 최선을 다하고 있습니다.

    See More
  • 전력

    1970년대 중반, Yokogawa는 EBS 전기 제어 시스템 (EBS Electric Control System)의 출시와 함께 전력 사업에 진출했습니다. 그 이후로 Yokogawa는 전 세계 고객에게 최상의 서비스와 솔루션을 제공하기 위한 기술과 역량의 개발을 꾸준히 지속해 왔습니다.

    Yokogawa는 역동적인 글로벌 전력 시장에서 더욱 적극적인 역할을 수행하기 위해 글로벌 전력 솔루션 네트워크를 운영했습니다. 이로 인해 Yokogawa 내에서 보다 긴밀한 팀워크가 가능해져서 글로벌 리소스와 업계 노하우를 하나로 모았습니다. Yokogawa의 전력 산업 전문가들은 각 고객에게 정교한 요구 사항에 가장 적합한 솔루션을 제공하기 위해 협력합니다.

    See More
  • 정수 및 하수 처리

    Yokogawa는 보다 효율적인 사회를 만들기 위하여 에너지 최적화 기술 개발, 온실가스 감축, 오염 물질로부터 환경을 보호하는 견고한 제품 제작 등을 통해 지속 가능한 수자원 생산을 위한 제어 솔루션을 제공하고 있습니다. Yokogawa의 첨단 기술과 폭넓은 애플리케이션 노하우를 통해 고객과 협력하여 사업을 활성화하고 플랜트 수명주기 전반에 걸쳐 높은 가치를 제공할 수 있는 지속 가능한 솔루션을 제공합니다. 당사의 기술과 제품은 플랜트의 성능을 향상시키고 오늘날의 수자원 시장에서 경쟁적으로 운영할 수 있도록 보장하며 운영비를 절감합니다. Yokogawa는 지자체 및 공업용수 처리 시장에서 광범위한 수처리 응용 분야를 지원합니다.

    See More
  • 제지 및 펄프

    제지 및 펄프 산업에서는 경쟁이 심하고 끊임없이 변화하는 시장 요구를 충족시켜야 합니다. Yokogawa는 이러한 시장 환경에서 전 세계적으로 지속 가능한 에너지 효율적 플랜트를 실현하는 데 도움을 줍니다.

    See More
  • 철강

    철강 산업에서는 제품뿐만 아니라 제조 및 운영 기술의 품질을 향상시키고 환경 및 에너지 효율 문제를 해결하는 것 또한 중요합니다. Yokogawa는 고객이 이상적인 플랜트를 만들 수 있도록 돕고 동반 성장을 위해 발전해 나가고 있습니다.

    See More
  • 특수화학 및 정밀화학

    Yokogawa는 오랫동안 특수 및 정밀 화학 시장에서 고객을 지원해왔습니다. Batch 솔루션 설계의 복잡한 요구 사항을 이해하는 업계 전문가는 물론 업계 최고 수준의 안정성과 유연성을 제공하는 시장 선도 일괄 처리 솔루션을 사용하면 Yokogawa와의 파트너십에서 안전 및 규정 준수를 유지하면서 고객의 요구 사항을 충족시키는 제품을 생산할 수 있습니다.

    See More
  • 폐수처리

    폐수 처리 설비는 많은 모터, 펌프, 송풍기 등을 사용하기 때문에 운전 비용을 줄이기 위해서는 전력 소비를 줄이는 것이 중요합니다. Yokogawa는 에너지 효율성을 높이기 위한 최적의 제어 솔루션을 제공합니다. 

    See More
  • 화력발전

    석탄, 석유 또는 가스를 연료로 사용하는 화력발전은 전 세계적으로 대부분의 전력을 생산하고 있습니다.

    See More
  • 화학

    화학 플랜트는 연속 및 Batch 생산 공정에 의존하며, 각각은 제어 시스템에 대한 다양한 요구 사항을 제시합니다. 연속 공정은 실패하지 않고 생산 라인을 중단시키는 견고하고 안정적인 제어 시스템을 필요로하는 반면, Batch 공정의 중요성은 수식, 절차 및 공정을 조정하는 데 있어 큰 유연성을 허용하는 제어 시스템을 갖추는 데 있습니다. 두 종류의 시스템 모두 제품의 사용 가능한 품질 내역에서 관리되어야 하며 비일상적인 작업을 수행할 수 있어야 합니다. Yokogawa는 광범위한 제품 포트폴리오, 숙련된 시스템 엔지니어 및 글로벌 영업 및 서비스 네트워크를 통해 모든 공장 공정에 대한 솔루션을 제공합니다.

    See More

Related Products & Solutions

  • Process Control PLC/RTU

    프로세스 공장에서 원격 위치에 이르기까지 당사의 공정제어 PLC 및 원격 터미널 장치 (RTU)는 사용자가 운영의 우수성을 극대화하도록 돕습니다.

    See More

Top