pH Measurement in Flue Gas Desulfurization Systems That Use Magnesium Hydroxide Slurry

다운로드 (172 KB)

Introduction

Flue Gas Desulfurization Process
Flue Gas Desulfurization Process

In flue gas desulfurization systems that use magnesium hydroxide (Mg(OH)2) slurry, the consumption of the desulfurization agent (Mg(OH)2) is controlled by using online pH analyzers. A great concern in the pH measurement is heavy staining of the pH electrodes by the Mg(OH)2 slurry. To ensure accurate measurement, frequent cleaning of the electrodes with an acid is required, adding to both maintenance workload and cost.

The EXA AUTO CLEAN chemical cleaning system automates the acid cleaning process, which not only saves both time and expense but also ensures precise pH measurement over long periods.

Expected Benefits

  • Improves the efficiency of a flue gas desulfurization system with Mg(OH)2 slurry
  • Ensures stable, continuous pH measurement
  • Reduces operating costs
  • Eliminates manual cleaning

Process Overview

In the flue gas desulfurization system, Mg(OH)2 is used as the absorbent to remove sulfur dioxide (SO2) from the flue gas.

Absorption reaction 1: Mg(OH)2 + SO2 ->MgSO3 + H2O
Absorption reaction 2: MgSO3 + SO2 + H2O -> Mg(HSO3)2

After absorbing SO2, the solution undergoes pH adjustment, oxidation, and filtration for detoxification before discharge.

pH adjustment: Mg(HSO3)2 + Mg(OH)2 -> 2MgSO3 + 2H2O
Oxidation: MgSO3 + 1/2O2 -> MgSO4

Solution Details

Measurement System & Operation Outline

Measurement System & Operation Outline

Field Data

When performing pH measurement in a flue gas desulfurization system with Mg(OH)2 slurry, the electrodes tend to become heavily stained by the slurry. The cleaning of the electrodes and the reduction of maintenance time and cost are key points to consider when selecting a pH analyzer for the system.

  pH System with Chemical Cleaning General pH Analyzer
Cleaning "Automatic acid cleaning: 2 or 3 times/day, user programmable Manual acid cleaning: approx. monthly" "Manual acid cleaning: once/day"
Calibration Manual calibration: weekly "Manual 2-point calibration: weekly"
Other maintenance Replenishment of chemical tank: approx. every 2 months -

Acid cleaning is done with a 4% hydrochloric acid solution.

업종

Related Products & Solutions

12mm Digital SMART pH Sensor SC25F

SC25F는 일체형 온도 소자와 액체 접지 전극을 포함하는 12mm 디자인의 디지탈 SMART pH 센서 입니다.

12mm pH Sensor SC25V

The SC25V는 12 mm 디자인의 pH 센서로 내장형 온도 소자와 액체 접지 전극을 포함합니다.

2-Wire Transmitter/Analyzer FLXA202/21

FLEXA ™ 시리즈 분석기는 산업용 설비의 연속 온라인 측정에 사용됩니다. 단일 또는 이중 센서 측정 옵션이 있어 가장 유연한 2 선식 분석기입니다.

4-Wire pH/ORP Analyzer PH450

PH450 pH와 ORP 분석계인 PH450은 pH와 온도, ORP(Redox) 측정을 결합한 다변형 분석계로, mA 전류 출력 2개, 독립적인 SPDT 접점 출력 및 HART 등 다양한 출력기능을 통해 활용할 수 있습니다. 

pH/ORP Sensors PH8EFP, PH8ERP, OR8EFG, OR8ERG

Yokogawa의 pH와 ORP 분석계는 높은 신뢰성을 제공합니다. 이 제품은 고급 기능을 갖추고 있으며 광범위한 생산 공정과 중규모 폐수 처리 시설의 수질관리를 비롯하여 일반적인 pH 및 ORP 제어시스템과 같은 다양한 어플리케이션에 유용합니다.

pH and ORP Analyzers

pH와 ORP 미터, 분석계 및 전송기는 수질/제품 품질을 보장하고 유출물 배출량, 배치 중화, 펄프 스톡, 세정기, 냉각 타워, 화학, 폐수 처리 및 기타 여러 어플리케이션의 연속 공정 모니터링에 사용합니다.

pH and ORP Sensors

pH 전극 및 센서는 pH 측정의 감지 부분입니다. Retractable, flow-though, 침적 및 직접 삽입을 포함한 다양한 설치 옵션이 있습니다.

적절한 pH 전극 / 센서 선택은 최적의 측정 결과를 위해 중요합니다.

×

Have Questions?

Contact a Yokogawa Expert to learn how we can help you solve your challenges.

Top