Impulse Line Blocking Diagnosis

Descargas (568 KB)

Introduction

Impulse Line Blocking Diagnosis in DP Transmitters

Figure1. Connected to impulse lines

Figure 1 Connected to
impulse lines

Differential pressure (DP) flowmeters composed of an orifice plate, a DP transmitter, and other components are widely used in many applications because they are reliable and require no wet calibration. The simple design of orifice plates and modern DP transmitters make them extremely reliable. However, the impulse lines which transmit process pressure to the DP transmitter are vulnerable to blockages caused by fluid condensation, freezing, or corrosion. Impulse line blocking is a problem that must be addressed to ensure efficient operation and maintenance.

Yokogawa's EJX series DP transmitter is equipped with a silicon resonant sensor that can rapidly detect both static pressure and differential pressure. These features enable the development of a diagnostic technique which detects fluctuations in static and differential pressures. By using a digital communications network such as fieldbus, operators can determine whether an impulse line at a specific installation site has been blocked. Such information can significantly reduce maintenance workload and cost.

Expected Benefits

  • Informs operators/maintenance engineers that a blockage is forming in an impulse line before the process is disrupted.
  • Predicts when the impulse line will be blocked and suggests a corrective action, based on blockage thresholds.
  • Blockage thresholds are determined based on blocking substance, flowrate variation, and the time required for taking corrective action.

Impulse-line-blocking Diagnostic Technique

(1) Fluctuation of differential, static pressures

Table 1. Fluctuating component values in impulse lines

Table 1 Fluctuating component values in impulse lines

Fluctuating components of differential, static pressures generally decrease when an impulse line is blocked.

Fluctuating components are calculated as the square summation of the difference of differential and static pressures that are sampled at very short time intervals. The amplitudes of fluctuating components are derived from the root of the square summation. Since these components are affected by flowrate changes, they are provided as fluctuation components through flowrate compensation.

Table1 shows the value of the fluctuating components when blocking occurs on the Hi-side, Lo-side, and both sides. The values for when no blocking occurs are also shown. When both sides of impulse lines are blocked, all fluctuating components decrease. When one side of an impulse line is blocked, the corresponding fluctuating component decreases. In this case the fluctuating component of differential pressure is larger than when no blockage occurs.

(2) Blocking diagnosis using water flow test rig

Figure 2. Blocking factor F with H and L side blocking

Figure 2 Blocking factor F with H and L side blocking

Blocking factor F is determined as the correlation function between the amplitudes of fluctuating components. It approaches +1 for high side blocking and -1 for low side blocking. Figure2 shows the Blocking factor F for each blocking type.

Conclusion

Operators must receive diagnostic information before a line block leads to a malfunction. Yokogawa provides predictive diagnostics based on trend analysis of the blocking factor, which improves maintenance efficiency and reduces maintenance costs.

Note:

This diagnostic function is currently available for low viscous liquids only.

Industrias

Productos y Soluciones Relacionadas

EJX110A

Transmisor de Presión Diferencial con montaje tradicional basado en la serie EJX-A.

EJX115A

Transmisor de Presión Diferencial unido a un IFO basado en la serie EJX-A.

EJX118A

Transmisor de Presión Diferencial con Sellos Remotos de Diafragma basado en la serie EJX-A.

EJX120A

Transmisor de Presión Diferencial con montaje tradicional diseñado para aplicaciones de Rango Corriente basado en la serie EJX-A.

EJX130A

Transmisor de Alta Presión Diferencial Estática con montaje tradicional basado en la serie EJX-A.

EJX210A

Los Transmisores de Presión Diferencial Montados en Brida diseñados para aplicaciones de Nivel Líquido de la serie EJX-A.

EJX310A

Transmisor de Presión Absoluta con montaje tradicional basado en la serie EJX-A.

EJX430A

Transmisor de Presión del Manómetro con montaje tradicional basado en la serie EJX-A.

EJX438A

Transmisor de Presión del Manómetro con Sello Remoto del Diafragma basado en la serie EJX-A.

EJX440A

Transmisor de Alta Presión del Manómetro con montaje tradicional basado en la serie EJX-A.

EJX510A

Transmisor de Presión Absoluta con Montaje en Línea basada en la EJX -A Series.

EJX530A

Transmisor de Presión del Manómetro Montado en Línea basado en la serie EJX-A.

EJX610A

Transmisor de Presión Absoluta de Alto Desempeño con Montaje en Línea basada en la Series EJX-A.

EJX630A

Transmisor de Alta Presión del Manómetro Montado en Línea basado en la serie EJX-A.

EJX910A

Este transmisor mide con precisión la presión diferencial, la presión estática, y la temperatura del proceso; además utiliza estos valores en un ordenador de flujo de alto desempeño para ofrecer Flujo Másico que está compensado.

EJX930A

Está diseñado específicamente para aplicaciones de alta presión estática, este transmisor mide con precisión la presión diferencial, la presión estática, y la temperatura del proceso; además utiliza estos valores en un ordenador de flujo de alto desempeño para ofrecer Flujo Másico que está compensado.

×

 

 

¿Tiene Dudas?

Contacte a un Experto de Yokogawa y conozca como podemos ayudarle a resolver sus retos.

Top