Reduction Monitoring in the Chromium Wastewater Treatment Process

Introduction

Wastewater from electroplating facilities and certain types of chemical plants contains toxic forms of hexavalent chromium such as chromate and dichromate. The hexavalent chromium in this wastewater must be reduced before the water can be discharged. This requires a two-step process: hexavalent chromium (CR6) is reduced to trivalent chromium (CR3); and CR3 is precipitated as chromium hydroxide. As the oxidation reduction potential (ORP) and the speed of the reduction reaction are closely tied to the pH value, ORP and pH analyzers are used to ensure proper control of the reduction process through such means as the injection of reducing agents.

pH and ORP measurements in these reaction tanks are complicated by the presence of chrome and sulfur dioxide, which can poison the sensor reference under certain circumstances. pH and ORP control in these applications may be conducted using alarm relays and a simple on/off control scheme such as available in the FLXA402 Analyzer. Alternatively, the 4-20mA current output can be used directly for proportional control, or sent to a distributed control system as needed. The FLXA202/FLXA402 can measure both ORP and pH. Both 2-wire and 4-wire analyzers are suitable for this measurement system. A gold electrode should be used for ORP measurement of chromium wastewater.

Reducing trivalent chromium process

Reducing trivalent chromium process

Expected Benefits

  • Measures pH/ORP of chromate wastewater continuously
  • Reduces operating costs

Process Overview

First, hexavalent chromium, either in the form of chromate or dichromate, is reduced to trivalent chromium. Wastewater flows into the first reaction tank, where the pH is measured and sulfuric acid is automatically brought into the process until a pH set point value in the acidic range is achieved. The reaction time is just a few minutes, and a lower pH for an even faster reaction would require considerably more acid. At the same time, the oxidation reduction potential (ORP) of the solution is measured, and sulfur dioxide (SO2), sodium sulfite, or sodium metabisulfite is automatically injected until an ORP value of approximately 280 mV is achieved.

Then in the second tank, the pH is raised to 8.5 by the addition of an alkaline solution such as ammonia or caustic (NaOH), where it is converted to chromium hydroxide. The precipitate, although heavier than the water, does not drop to the bottom due to agitation in the tank. The mixed slurry flows to a settling tank, where the trivalent (Cr3+) chrome settles to the bottom and the clear chromium-free water flows over the tank for further treatment. Chemicals known as coagulants are sometimes added to the second reaction tank to help form larger particles and aid in sludge removal. The reducing agent may be a substance such as ferrous sulfate, sodium metabisulfite, or sulfur dioxide. Chemicals known as coagulants are sometimes added to the second reaction tank to help form larger particles and aid in sludge removal.

Solution Details

Measurement system

2-wire/4-wire pH/ORP measurement system

Sensor
KCl refillable ORP sensor: OR8EFG-AU-☐☐-TT1-☐*A
KCl refillable pH sensor: PH8EFP-☐☐-TN-TT1-N-☐*A
Submersion type holder: PH8HS-PP-☐☐-T-NN-NN*A
Terminal box (when needed)
WTB10-PH1 (for 2-wire system)
WTB10-PH3 (for 4-wire system)
Converter/transmitter:
2-wire transmitter (pH/ORP): FLXA202-D-BーD-☐-P1-NN-A-N-LA-☐-NN
4-wire pH/ORP converter: FLXA402-A-B-□-P1-NN-A2-WR-☐-☐-☐-NN

Measurement Conditions

Measurement conditions
Measurement conditions
  1. Check solutions for ORP analyzer
    Oxidation-reduction potential of check solutions (quinhydrone/iron solutions)
    A check solution is used to determine whether the ORP sensor is operating correctly. There are two types of check solutions: quinhydrone and iron.

    Quinhydrone solution: approx. 200 to 300 mV
    Iron solution: approx. 420 to 520 mV
    Unlike a pH standard solution, an ORP check solution does not always indicate a constant reference value. Whether the sensor is operating normally can be determined by seeing whether its readings are within the acceptable range.
    Preparation of a check solution (250 mL)
    Quinhydrone solution: Dissolve the following reagent in pure water and dilute to 250 mL.

    Quinhydrone salts: P/N K9024EC

    Ferrous & ferric: dissolve the following reagent in a 2-mol/L sulfuric acid solution and dilute to 250 mL.

    Ferrous & ferric salts: P/N K9024ED
     
  2. Use of a gold electrode for ORP measurement
    For ORP measurement of chromate wastewater, the use of a gold electrode is recommended.

Industrieën

  • Afvalwater behandeling

    Afvalwaterzuiveringsinstallaties gebruiken veel motoren, pompen, blowers, enz. . Daarom is het belangrijk om hun elektriciteitsverbruik te verminderen en zo de bedrijfskosten te verlagen. Yokogawa levert optimale besturingsoplossingen om de energie-efficiëntie te verbeteren.

    Meer
  • Water en afvalwater

    Waterbronnen zijn eindig en daarom is het bijdragen aan een duurzame watercyclus een van de duurzame ontwikkelingsdoelen (SDG's). Yokogawa levert al jaren geavanceerde digitale besturingsoplossingen voor de stabiele levering van schoon en veilig water en de behandeling van afvalwater ter bescherming van het watermilieu. Maar ook het beheren van waterverliezen en de optimalisatie van de werking van installaties ter vermindering van de CO2-uitstoot en de bedrijfskosten.

    Yokogawa ondersteunt een breed scala aan waterbesturingstoepassingen in zowel waterschappen als de industriële watermarkt. Met onze toonaangevende technologieën, betrouwbare producten, uitgebreide expertise en ervaring met diverse waterprojecten over de hele wereld, werken wij met u samen om duurzame wateroplossingen te bieden die uw bedrijf een impuls geven en waarde toevoegen gedurende de gehele levenscyclus van de installatie.

    Meer
  • Waterbehandeling

    Yokogawa levert optimale oplossingen om de betrouwbare werking van waterbehandelingsinstallaties te verbeteren. Deze oplossingen omvatten geavanceerde technologieën, onovertroffen productkwaliteit, en uitgebreide applicatie kennis gedurende de gehele levenscyclus.

    Meer

Gerelateerde producten & oplossingen

  • 2-Wire Transmitter/Analyzer FLXA202

    The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.

    Meer
  • 2-Wire Transmitter/Analyzer FLXA21

    The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.

    Meer
  • Digital SMART SENCOM™ Adapter, SA11

    Reusable SMART adapter, requiring only the analog sensor to be disposed of when it reaches the end of its lifetime. With the SENCOM 4.0 platform, Yokogawa delivers reduced costs and waste while contributing to its long-term business goals of a sustainable future for all.

    Meer
  • Multi Channel 4-Wire Analyzer FLXA402

    The FLEXA™ series analyzers are modular-designed analyzers used for continuous online measurements in industrial installations. They offer single or multi-sensor measurement.

     

    Meer
  • pH and ORP Analyzers

    pH and ORP meters, analyzers and transmitters are used for continuous process monitoring of pH and ORP to ensure water/product quality, monitor effluent discharge, batch neutralization, pulp stock, scrubbers, cooling towers, chemical, water/wastewater treatment and many other applications.

    Meer
  • pH and ORP Sensors

    pH electrodes and sensors are the sensing portions of a pH measurement. Various installation options including retractable, flow thru, immersion, and direct insertion. Proper pH electrode/sensor selection is critical for optimal measurement results.

    Meer

Top