YFGW510/YFGW520現場無線接入點以國際自動化協會(ISA)的工業自動化無線通信標準ISA100.11a為基準。該產品具有符合ISA100.11a標準的主干路由器功能,與現場無線管理站(YFGW410)和/或現場無線媒體轉換器(YFGW610)組合,構成現場無線系統。YFGW520是YFGW510的後續產品,可實現強大而長距離骨干網建設。
- 世界最小級别的高性能工業無線繼電器設備:
本產品基於多種無線標準,是世界最小級别的工業無線繼電器設備。因此,本產品可擴展現場無線網絡,並提供可靠的通信。 - Duocast (ISA100.11a 標準):
本產品具備符合ISA100.a標準的Duocast功能。通製與2台YFGW510同時接收數據,可以增強現場無線通信的可靠性。 - 穩定的工廠局域網:
YFGW520支持兩種光纖通信選項,通製與YFGW610相結合,可以構建一個抗噪,長距離(最長5 km)的骨干網。
Details
通信接口 | 標準 | IEEE802.15.4 |
---|---|---|
頻率 | 2400–2483.5MHz | |
通信速度 | 250kbps | |
無線電安全性 | AES128bit | |
輸出功率 | 最大10dBm | |
接頭 | N 型 | |
電纜類型 | 同軸 | |
端口 | 1個端口 | |
保護 | - | |
通信協議 | F現場無線 | ISA100.11a |
管理/配定等 | - |
通信接口 | 標準 | IEEE802.11a/b/g2 | 100Base-TX | 100Base-FX |
---|---|---|---|---|
頻率 | b/g: 2400-2483.5MHz, a: 5150-5850MHz | - | - | |
通信速度 | 1~54Mbps | 100Mbps | 100Mbps | |
無線電安全性 | WPA2-PSK | - | - | |
輸出功率 | 最大 15dBm | - | - | |
接頭 | N型 | RJ-45 | SC 接頭 [ 單極 × 2 ]3 | |
電纜類型 | 同軸 | 類别5 | 多模光纖*6 單模光纖*6 | |
端口 | 最多2個端口 | 1個端口 | 1個端口 | |
保護 | - | 浪湧 | - | |
通信協議 | 現場無線 | - | - | - |
管理/配定等 | IEEE1588PTP v24, 橫河專用5 | IEEE1588PTP v24, 橫河專用5 | IEEE1588PTP v24, 橫河專用5 |
- 在室外接線至現場網絡或現場無線主干網100BASE-TX時,使用非金屬拉力構件的光纖連接YFGW610。
- 在現場無線主干網中使用無線LAN時,本產品與現場無線管理站YFGW410之間需要有無線LAN接入點。
- 由於受到導管孔口徑的限制,所以不能使用2極SC接頭。SC接頭應使用Short Boot型。
- 在一個現場無線子網中安裝YFGW410和多台本產品時,可以選擇直接連接或通製IEEE1588PTP基礎產品進行連接。
- 基於TCP的定制協議用於本產品與YFGW410之間的通信。
- YFGW510僅支持多模光纖,YFGW520支持兩種光纖通信選項。
功能規格 | Te溫度範圍ge | 運行時: -40 to +65°C (海拔高度:最高3000米) 存儲時: -40 to +85°C |
---|---|---|
H濕度範圍ge | 運行時::5 to 95 %RH (無結露) 存儲時: 5 to 95 %RH (無結露) | |
Te溫度變化率nt | 運行時:≤10°C/h 存儲時:≤20°C/h | |
P電源ly | 電壓範圍: 10.0~26.4 V DC 額定電壓: 24 V DC M瞬時斷電:瞬時斷開連接 直流電源波速比:≤1%p-p | |
Po功耗ion | 最大3.5 W | |
G接地g | D級接地(不要與其他儀表共用接地線) | |
冷卻方式g | 自然空氣冷卻 | |
Reg強制合規性聲明ts | Regul無線模組的強制一致性標準le |
|
R&TTE 一致性標準s |
| |
Saf安全要求nts | CSA C22.2 No. 61010-1 | |
Exp防爆類型ed Types | FM, CSA 非易燃認證oval ATEX n類聲明 IECEx n類認證 ATEX, IECEx 隔爆認證 FM(美國或加拿大):隔爆認證(申請中) |
參考
One important risk to manage with regard to coal stacks is preventing fires due to spontaneous combustion.
Wireless Multi-Input Temperature Transmitter YTMX580 can accept inputs from up to 8 points, and contribute to your CAPEX cost reduction.
Delayed Coker is a type of coker who's process consists of heating residual oil feed to its thermal cracking temperature in a furnace. The most important variable in industrial furnace control is temperature. Temperature is measured throughout the furnace in different zones and temperature effects the materials being manufactured and therefore must be precisely monitored to prevent deviations in quality of the final product.
Eliminating the wire using wireless transmitter is the perfect solution for rotating equipment. It establishes data collection between the transmitter and the gateway by reliable communication even though the dryer was rotating.
Blending plays a key role in industries such as food, healthcare and chemicals etc. Temperature and vacuum measurements are very important in minimizing the moisture content to ensure the quality of the final product. Strictly maintaining them throughout the process ensures the final product yield.
Direct Reduction Iron (DRI) is one of the processes to reduce oxygen from iron oxide pellets for steel plant. More than 90% of DRI processes use heated LNG as process gas where PID control for temperature or interlock control is of vital importance.
Pressure measurement of tubeless tyres to monitor the air loss is one of the key performance tests in the tyre manufacturing units. Relocation of tyres from one testing rack to the other for various tests and frequent movement of the testing setup for conditional tests to various locations calls for cable free implementation for ease of handling.
Wireless technology has a long history, and it began around the time that James C. Maxwell theoretically predicted and then proved the existence of electromagnetic waves in the 1860s, and when Heinrich R. Hertz experimentally confirmed the actual existence of the electromagnetic wave in 1888.
In plant sites, there are various places such as those affording an unobstructed view like tank yards, and others surrounded by metal pipes and equipment obstructing the view (hereafter referred to "pipe jungles"), often seen in oil refinery and chemical on-site plants. The frequency band of radio waves used for field wireless communication is 2.4 GHz, which has high straightness and its ability to go around things can hardly be expected.
The introduction of wireless technologies into plants is anticipated as one of the measures for implementing field digital solutions not only to reduce cable wiring costs but also to improve plant wide safety/stable operations, operating efficiency, and so on.
As compared to Distributed Control Systems (DCS) such as CENTUM VP that monitors the operations of the overall plant, PRM is a type of Plant Asset Management (PAM) software package that primarily focuses on the maintenance of devices and instruments.
The FieldMate versatile device management wizard is PC software mainly used for configuring and adjusting field devices. Under the concept of "one tool for all," Yokogawa has been enhancing this software to support a wide range of field devices and field communication protocols.
In recent years, expectations for control systems using wireless communications have been increasing in the process control market. This is because these systems do not require power and communication wiring for field instruments, enabling reduced initial and maintenance costs, and easy installation.