digitalYEWFLO Fieldbus Type Vortex Flowmeter

Yokogawa’s proprietary filter (SSP) for digital signal processing analyzes vortex signals and automatically selects the optimum settings for the best possible measurement.

Product Information

digitalYEWFLO Fieldbus Type Vortex Flowmeter

digitalYEWFLO Fieldbus Type Vortex Flowmeter logo
Fieldbus is a two-way digital communication system. It is a revolutionary technology for configuring instrumentation control systems and a promising successor to the standard 4 to 20mA analog communication used in most field instruments today.  By combining Fieldbus communications with digitalYEWFLO's ability to simultaneously output analog and pulse readings for flowrate, temperature, mass flowrate and total flowrate, a greater variety of powerful flow control applications are possible.
 
 
  digitalYEWFLO Series catalog
 
  DY and DYA Vortex Flowmeter FOUNDATION™ fieldbus Communication Type General Specifications
 
  List of digitalYEWFLO Vortex Flowmeters general specifications
 
  List of digitalYEWFLO Vortex Flowmeters drawings
 

Features: digitalYEWFLO Fieldbus Type Vortex Flowmeter

Interoperability (ITK 5.0.1)
  FOUNDATION Fieldbus specifications (ITK 5.0.1) grant the interoperability of the field instruments.
 
Reduction of instrumentation cost
  The multi-drop wiring on the Fieldbus communication line contributes to the reduction of wiring cost.
 
Mass flow calculation
  Arithmetic (AR) function block expands the mass flow calculation function for the saturated steam, superheated steam, gases and natural gas by using external pressure/temperature input (/MV:internal temperature input) with a high accuracy. Additionally, in combination with DTM* brings to the high accurate mass flow calculation output, ex. natural gas process.
 
User-friendliness
  The common function block of field devices have the same operability, because of their common specification. The individual device setting (Transducer Block parameter setting) can be done simply by executing METHOD.
 
Independent flow and temperature calculations (multi-variable type: option)
  The multi-variable type (/MV: option) of digitalYEWFLO separately outputs flowrate output (AI1) and temperature output (AI2) . Two DI function blocks output the limit signal output both flowrate and temperature.
 
Advanced self-diagnostics
  The digitalYEWFLO has advanced self-diagnostics which can predict and identify anomalies in the process conditions, such as high pipeline vibration and abnormal flow. Also, the Fieldbus type digitalYEWFLO supports various alarm functions, such as high/low-limit alarms and alerts of block errors, based on the FOUNDATION Fieldbus specification.
 
Link Master function : BASIC at factory setting.
  digitalYEWFLO Fieldbus models support the Link Master function. This function enables backup of network manager and local control only by field devices.
 
PID function block (option)
  A PID function block (with the I-PD control algorithm) enables the field device to control the process.
 
Software download function (option)
  Software download function permits to update DY software via a FOUNDATION fieldbus. Typical use of this function is to add new features such as function blocks and diagnostics to existing devices.
 
  * DTM (Device Type Manager): the application which defines the Graphical User Interface (GUI) specific to the device.

Specifications: digitalYEWFLO Fieldbus Type Vortex Flowmeter

All DY and DYA models are Fieldbus enabled (output code: F) and conform to the EN61326-1 Class A, Table 2 (For use in industrial locations), EN61326-2-3, EN55011 Class A Group 1 EMC standards
  digitalYEWFLO Fieldbus Type Vortex Flowmeter
Output signals Digital communication signals compliant with the FOUNDATION™ fieldbus protocol
Supply voltage 9 to 32 V DC for general-purpose and flameproof types
9 to 24 V DC for intrinsically safe type (Entity model)
9 to 17.5 V DC for intrinsically safe type (FISCO model)
Communications line Supply voltage: 9 to 32 V DC
Supply current: 15mA (maximum)
Function specifications
Function blocks
  AI function blocks (3):
    AI1: monitors the flowrate and totalized flow rate
    AI2: monitors the temperature (if the multivariable type)
    AI3: volumetric flow input for mass flowrate calculation of AR.
  DI function blocks (2):
    for flow and temperature limit switches
  AR function blocks (1):
    mass flow calculation
  IT function blocks (1):
    integrates a variable as a function of the time or accumulates the counts
  PID blocks (1):
    for models with LC1 option
*Combination with multivariable option (/MV) is available.
Hazardous area classifications TIIS / FM / CENELEC / CSA / SAA


Please see Features of digitalYEWFLO for common items.