YS170 Peer-to-Peer Communications

Overview

Peer-to-peer communications can be defined as the ability to digitally share data between two or more like devices, without the need of a master/slave relationship. Peer-to- peer allows selected data points to be shared continuously without the need to request and read data. YS170 (Style 3 or higher) has an option for peer-to-peer communications, model suffix /A33. YS-Net is the name for the communications network. Any address in a YS170 program can be transmitted via YS-Net to other YS170's. YS-Net peer-to-peer is pre-configured, allowing four (4) YS170 controllers to transmit up to four (4) analog values and sixteen (16) status points each to up to sixteen (16) controllers resident on the network. Refer to Figure 1.

Figure 1

Figure 1

YS-Net (Peer-to-Peer)

This new network incorporates state-of-the-art communications using Echelon® LONWorks. In the pre-configured peer-to-peer mode, YS-Net operates at 78.125 Kbps over a single twisted pair of wires (nominal AWG 22) at a cable length up to 4000 feet. The Neuron® chip, the brains of LONWorks, can be configured to operate in many desired manners using a software development kit. The pre-configured peer-to-peer format described above is the standard offering, but alternative configurations may be designed for specialized applications.

Why LONWorks?

LONWorks has been selected by more than 1000 companies to meet the communications needs in their specific equipment. The Neuron® chip is manufactured by both Motorola and Toshiba, guaranteeing availability. A PROM used with the Neuron® chip can be modified for unique requirements. And the chip is inexpensive to purchase and implement! Future considerations may be digital communications to external devices, e.g., relay or signal conditioning modules.

Why Use Peer-to-Peer?

Peer-to-peer communications allows analog and status values in up to four YS170's to be transmitted to others. This cross-talk allows more sophisticated control and interaction within a "system" of YS170 controllers. Analog or discrete inputs/outputs can be distributed, extending I/O capabilities. Installation and wiring costs are lowered.

Implementing YS-Net

Style 3 and higher YS170 Dual Loop Programmable Controllers are offered with YS-Net peer-to-peer communications as an option (/A33). The actual communications instructions are written into the YS170 custom program. New addresses are available:

  • CY01-16: analog outputs
  • CX01-04: analog inputs
  • CO01-16: status inputs
  • CI01-64: status outputs
  • CF01-04: communications failure

No other configuration is required. Upon commissioning, the YS170 controller identifies the presence of a YS-Net card (/A33) and the communications configuration is automatically installed.

YS-Net Addresses

Both analog and status (digital) data can be transmitted via peer-to-peer. YS170 controllers with addresses 1 to 4 serve as transmitters and receivers. Addresses 5 to 16 serve as receiving devices only. The communications address number must be set on the CONFIG 1 display of the YS170 controller. Each controller must have a different YS-Net address, 1-16. Refer to Figure 2.

Communication Addresses

Figure 2
Figure 2

Analog data from YS170 address 1 can be read by another device using communications input registers CX01-04 in the receiving controller program. CX05-08 are parameters sent from controller 2, CX09-12 for 3, and CX13-16 for 4. Remember, only the first four controllers on the YS-Net highway can transmit data, YS170 addresses 1-4.

Example:

  • LD CX01 Analog data from CY01, controller #1
  • ST MV1 Data stored to receiving YS170 control output 1
  • LD CX06 Analog data from CY02, controller #2
  • ST SV1 Stored to set point 1

The transmitting YS170 analog data is written to output registers CY01- 04. The registers are the same for all four sending devices. The receiving controllers can differentiate the data from each controller using CX01-16, as described above.

Example:

  • LD SV2 Set point value
  • ST CY01 YS-Net send data
  • LD MV1 Control Output
  • ST CY02 YS-Net send data

Status inputs are identified as CI01- CI64. The same logic applies as described with analog values, i.e., CI01-16 are status inputs from controller 1, CI17-32 from controller 2, etc. Inversely, CO01-16 are status outputs from each of the transmitting controller, addresses 1- 4.

Example:

  • LD CI01 YS-Net status input controller 1
  • ST CAMF1 Auto/manual status receiving YS170
  • LD CAMF1 Auto/manual status
  • ST CO01 YS-Net status output

Communications failure flags (CF01- 04) are available. Each flag number designates the transmitting device address where communications has been interrupted. The flag is activated after 2 seconds and can be used in the receiving controller program to initiate a shutdown sequence or other fail-safe condition. The last transmitted data is retained or a dummy value can be installed to allow continued operation.

Example:

  • LD CF01 Comm flag #1
  • ST DO1 Discrete Output 1
  • GIF @SHUTDOWN
  • Begin shutdown logic

Refer to Table 1 for quick reference.

CX01-04

Analog inputs from #1

CX05-08

Analog input from #2

CX09-12

Analog inputs from #3

CX12-16

Analog inputs from #4

CY01-04

Analog outputs from #1-#4

CI01-16

Status inputs from #1

CI17-32

Status inputs from #2

CI33-48

Status inputs from #3

CI49-64

Status inputs from #4

CO01-16

Status outputs from #1- #4

CF01-04

Comm. FAIL from #1- #4

Table 1

YS170 Programming Software

The YS170 programming software package, Model YSS10-210, used to write custom control programs, is required. The version level must be 3.03 or higher. This allows the communications registers (CX, CY, CI, CO & CF) to be included in the program. Earlier software versions do not allow use of these registers.

Summary

YS-Net peer-to-peer communications provides the ability of interactive control and input/output expansion. It is easy to implement with no special configuration requirements. The YSS10-210 Version 3.03 or higher Programming Software Package is used to include the communications registers in the YS170 controller program. Peer-to-peer configuration is automatically installed. Simple to use and implement: YS-Net peer-to- peer communications.

Industrias

  • Agua y agua residual

    Yokogawa ha estado suministrando soluciones de control para la producción hídrica sostenible desarrollando tecnología con mayor eficiencia energética, ayudando a reducir la huella de carbono de las operaciones y fabricando productos de gran solidez que protegen el ambiente contra los contaminantes. Con nuestra tecnología de vanguardia y amplios conocimientos de las aplicaciones, trabajamos con usted para proveer soluciones hídricas sostenibles que impulsen su negocio y agreguen alto valor a lo largo del ciclo de vida de la planta. Nuestra tecnología y nuestros productos mejoran el desempeño de las plantas y garantiza que puedan operar competitivamente en los mercados del agua de hoy, así como reducir sus costos operativos. Yokogawa brinda apoyo en una amplia gama de aplicaciones para el control del agua en los mercados del agua tanto públicos como privados.

    Leer Más
  • Energía

    A mediados de la década de 1970, Yokogawa inició su participación en el negocio de la energía con el lanzamiento del Sistema de control eléctrico EBS. Desde entonces, Yokogawa ha continuado firmemente con el desarrollo de nuestras tecnologías y capacidades para proveer los mejores servicios y soluciones a nuestros clientes en todo el mundo.

    Yokogawa ha operado la red de soluciones de energía globales para jugar un papel más activo en el dinámico mercado de energía global. Esto ha hecho un posible un trabajo en equipo más unido dentro de Yokogawa, el cual conjunta nuestros recursos globales y nuestra especialización en la industria. Los expertos en el sector de energía de Yokogawa trabajan juntos para brindar a cada cliente la solución que se adapta mejor a sus requerimientos sofisticados.

    Leer Más
  • Petroquímica y a granel

    Las empresas productoras de petroquímicos, productos inorgánicos o productos intermedios se encuentran bajo una presión constante para equilibrar los costos y los márgenes al suministrar productos a sus clientes de manera oportuna y eficiente, manteniendo al mismo tiempo operaciones seguras y conformes con la normativa. Además, las empresas químicas tienen que adaptarse a la constante fluctuación de los precios de los insumos y la energía y tener la capacidad de proveer al mercado la combinación de productos más rentable.

    Yokogawa ha estado supliendo las necesidades de automatización del mercado de productos químicos a granel globalmente y ha obtenido reconocimiento como líder en este mercado. Con productos, soluciones y especialización en la industria, Yokogawa entiende su mercado y las necesidades de producción y trabajará con usted para proporcionarle una solución confiable y rentable durante el ciclo de vida de su planta.

    Leer Más

Productos y Soluciones Relacionadas

  • Single Loop Controllers

    Single loop controllers receive temperature, flow rate, pressure, and other types of measurement readings from sensors and send corresponding instructions to control elements such as valves in order to maintain these values within a desired range.

    Leer Más
×

 

 

¿Tiene Dudas?

Contacte a un Experto de Yokogawa y conozca como podemos ayudarle a resolver sus retos.


Top