The HXS10 combines the best of Yokogawa's measurement and control technologies. The measurement system is inherited from Yokogawa's recorders that are used in mission critical applications throughout the world; while the control engine comes from Yokogawa's highly reliable loop controllers that have been proven and refined for over 30 years.
HXS10 Application Specific Controller
HXSS10 Setting software for HXS
HXSS90 Proprietary cable for HXS
Optimally-designed field control device that combines proven robust measurement and control technologies.
- Built-in Solar Position Algorithm
- Sunrise, Sunset, and Solar Culmination time calculation functions available
- Open loop/closed loop hybrid control available
- Excellent Environmental Performance
- Operable even in a fanless box in the field
- Low power consumption (5 W or less) at a wide range of operating temperatures (-20 to 70°C)
- User Programs Meet a Wide Range of Requirements
- A wealth of arithmetic functions (trigonometric functions, PID, comparison, alarm, filter, etc.)
- Ability to create user algorithms
- Hardware Design Enables Optimization
- Customized hardware configuration to avoid unnecessary input, output and communication port costs.
- High Quality and Reliable Support
- High quality controllers with advanced diagnostics backed by Yokogawa's global support team ensure reliable operation.
Details
I/O Functions
Analog and digital I/Os, pulse counter input
User Programming and Maintenance
- Programming tool for easy function creation.
- Batch download to multiple HXS10 controllers via Ethernet
- Individual settings and diagnostics via a maintenance port.
Communication Function
The HXS10 peer to peer communication function reduces the communications load of higher-level systems.
Solar position algorithm (SPA) | Built-in NREL* SPA algorithm *National Renewable Energy Laboratory |
---|---|
Analog inputs | 0, 2, 4, or 6, isolated-channel, universal inputs (TC, mV, V, and RTD) |
Analog outputs | 0 or 2, 0-20 or 4-20 mA |
Digital inputs | 12 |
Digital outputs | 12 |
Pulse counter inputs | 0 or 2 (encoders), encoder input available |
Control periods | 250 or 100 msec (when using 2 or less analog inputs) |
Measurement period | Synchronized to control period |
Programming functions | Arithmetic operations, trigonometric functions, PID, alarm, filter, delay, time/numerical value comparison, branching, resistor operation, etc. |
Communication | Ethernet x1, maintenance port x1, RS232 (option), RS485 (option) |
Power supply | 24 VDC |
Power consumption | 5 W or less |
Operating temperature range | -20 to 70°C |
Dimensions | 226 mm (W) x 132 mm (H) x 67 mm (D) |
Applicable standard | CE mark, C-Tick |
Resources
Granite Power is a geothermal company that has developed GRANEX®, a patented direct supercritical fluid heat transfer technology for the efficient, eco- nomic, and zero carbon emission generation of electricity from low grade geothermal sources using the Organic Rankine Cycle (ORC).
- FAST/TOOLS SCADA system to remotely monitor the optimization of the process and make any required engineering changes to the live system.
- The Yokogawa control system (FAST/TOOLS, STARDOM, HXS10) monitors not only the sunlight but also the weather conditions.
Downloads
Instruction Manuals
- *Discontinued: Model HXSS90 (A1059UR) Proprietary Cable for HXS10 Precautions on the Use (517 KB)
- *Discontinued: Model HXS10 Application Specific Controller (1.2 MB)
- *Discontinued: HXSS10 Setting Software for HXS10 Installation Manual (2.0 MB)
- *Discontinued: HXSS10 Setting Software for HXS10, HXS10 Communication Interface (27.9 MB)
- *Discontinued: Notice of Alterations : HXSS10 Setting Software for HXS10, HXS10 Communication Interface (417 KB)
General Specifications
Looking for more information on our people, technology and solutions?
Contact Us