UP150
Avviso: Questo prodotto non è più disponibile dal…. Vedi questo prodotto sostitutivo

Compact 1/16 DIN sized Program Temperature Controller offers one program pattern with 16 segments. It also features universal input, two event outputs, auto-tuning and "SUPER" overshoot suppress function as standard. Retransmission output and RS485 communication are optional features.

The UP150 Program Temperature Controller (1/16 DIN size) is a compact, easy programming ramp-soak control and operation instrument. The UP150 has capability of one program pattern consisting of 16 segments, an auto tune and the "SUPER" overshoot suppress function as standard function. The two event outputs are provided as standard, and the external contact input, retransmission output and communication function are available as optional features.

  • Small, space-saving 1/16 DIN package, 48 (W) x 48 (H) x 100 (D) (mm)
  • Large 4-digit LED display
  • IP65 splash-proof and dust-proof designed front panel
  • Universal input for Thermocouple, RTD and DC mV/V signals
  • Capability of one program pattern consisting of 16 segments
  • Standard two event outputs
  • Optional retransmission output of measured value (PV)
  • Optional external contact input
  • Standard universal power supply (100 V to 240 V AC) and optional 24 V AC/DC power supply
  • Optional RS485 communication function, MODBUS, PC-Link & Ladder protocols are supported
  • RoHS Compliant

Resources

Check that the operating parameters UPR and DNR are both OFF.
Set both item P on the heating side and item Pc on the cooling side to 0.0.
If you set + dead zone in the settings, you can get an area where no outputs occur. If you set - dead zone, you can get an area where both outputs occur at the same time.
It depends on the model. The following lists the readable registers by model. UT100 series: D0001–D0009 UT300 series: D0001–D0008 UT400/UT500/UT700 series: D0001–D0025 UP350: D0001–D0008 UP550/UP750: D0001–D0025 ...
The PV value can be written by using the ladder sequence function of UTAdvanced series. However, when communication is interrupted, the PV value is retained.
If the operation mode is STOP or MAN, they are not displayed.
This is a limit on the number of times you can write to the element used (EEP-ROM).
Set them in the order, Alarm type → Alarm setting values. They will also not be displayed if you select an alarm for which no value is set.
The are set with a real number. For temperature, it is set in degrees Celsius.
Check whether the wiring to the power supply terminal is correct. If only the LCD on the UT/UP700 does not display, a custom computation may be set for no display. If the PV display is also blank, this may indicate product failure. Please contact you...
The output is 0% if there is a hardware failure such as an internal microprocessor.
PCBs (polychlorinated biphenyl) were banned from manufacturing and imports in 1975. The GREEN series began to be manufactured in 1997, and do not include PCBs.
There are 2 types of output available, FAIL and "failure diagnosis."
The sensor wire on the input side might be broken or disconnected.
No. When an alarm occurs, it automatically recovers if values enter the normal range.
What are energize/de-energize alarms?
(ns-faq-green-9076-term)
For energize alarms, ON contact results when an alarm occurs. For de-energize alarms, OFF contact results when an alarm occurs. Note that OFF contact also results when the power fails.
Yes, the Auto tuning function.
Ladder communication is used when communicating with the Computer link unit/Serial communication unit. Modbus/RTU is used for communication with the Modbus communication module.
Do Green series controllers support Ethernet?
(ns-faq-green-9009-connect)
Yes. This requires an RS-485/Ethernet converter such as VJET. The controller must also have a communication option. Some models can be connected directly with the UTAdvanced series.
How do I change the input type?
(ns-faq-green-9014-spec)
If you change the input type, parameters will be initialized. We do not recommend that you make changes while in operation.
Yes, but if you change some parameters, others will be initialized. We do not recommend that you make changes while in operation.
This is a protocol for communication with general purpose PCs and graphic panels. The UT130/UT150 can communicate with standard PCs. ...
Ladder communication is a protocol for communication with PLCs. Aside from Yokogawa PLCs, you can communicate with Mitsubishi MELSEC-Q/A series calculator link units (using A1SJ71UC24-R4 or A1SJ71C24-R4). ...
This is an overshoot suppression function that uses fuzzy logic. It constantly monitors deviation, and if it detects the possibility of an overshoot, it automatically changes the set point to a somewhat lower temp value (sub set point SSP). When y...
This is a protocol for communication with general purpose PCs and graphic panels, and also the FA-M3: You can communicate with Yokogawa PLC range free controller UT link modules and serial communication modules. Also, you can easily connect with PLCs...
These cannot be set when in Custom Computation mode.
What are direct and reverse action?
(ns-faq-green-9017-term)
Generally, reverse action means heating control and direct action means cooling control. When output is reverse action, output is ON during PVSP.
Almost all items can be accessed, including PV reading, SP writing, and PID setting.
Sample programs and dedicated communication materials are available for MELSEC-A/MELSEC-Q.
Yes, MELSEC-A, MELSEC-Q, and MELSEC-FX.
600 Ω.
There is no current input range.
(ns-faq-green-9018-spec)
Use a resistor to input current as voltage. A resistor is available: X010-250-2 (250 Ω).
If control is unstable after turning ON the power, this controller function automatically determines the optimal PID constant and restores control to a favorable state. Like auto tuning, this is a safe method that does not disturb the item being cont...