What does the specification, "Signal supply rating 15 VDC, 30 mA" mean?

The input types are non-voltage contact and open collector. Hence, it is not necessary to input a voltage to pulse input. This specification shows the withstand voltage and current capacity determined for contacts or transducers. In other words, a contact or transducer is needed that does not short even when 15 V is applied when OFF, and that does not short even when 30 mA flows when ON. Actually, at 5 V, 2.8 mA–3.8 mA, it is ON.

Súvisiace produkty a riešenia

  • DR130

    The DR130 can record data in 10 colors from all measurement points at 2-second intervals. It has a variety of recording functions including analog trend recording over an effective recording width of 150 mm, recording of digital measured values, recording of various messages, zone recording, and partially compressed and expanded recording, thus enabling data to be read off speedily.