The New Software Technologies Of CENTUM CS 3000

Download (42 KB)

TERASHIMA Nobuhiko1 KAWASHIMA Tetsuya2 KAKIMOTO Mamoru2 TANAKA Mihoko2

The new CENTUM CS 3000 distributed control system for large-scale plants incorporates the new technologies of OPC, DCOM, ActiveX and Web browsers to offer interoperability through standard data access interfaces and component embedding technology. These new technologies are essential for the CENTUM CS 3000 as a platform to supply solutions.

  1. Process Information System Center
  2. Process Control System Center

INTRODUCTION

Figure 1 Conventional Client/Server Architecture
Figure 1 Conventional
Client/Server Architecture

In this day and age, just simply buying a personal computer, taking it home and turning it on will enable you to be taken to the world of Internet. In such an era, communication connection capability and prospects is increasing in importance. DCSs are no exception for concern. Advanced computerization is also required in manufacturing sites.

In a plant, a DCS is an intelligent piece of equipment that has control functions and works on the front line of a manufacturing site as well as acting as a centralized warehouse for storing manufacturing information. Although this information is important since production planning and scheduling, cost calculations, and business analyses are performed based on it, there has until recently been no general-purpose interface between a DCS and upper-level systems. The integration of a DCS with an MES and ERP has been difficult.

BACKGROUND OF INCORPORATION OF NEW TECHNOLOGIES

Figure 2 Client/Server Architecture using OPC
Figure 2 Client/Server
Architecture using OPC

DCSs are required to be systems that can be integrated into a highly computerized society. Information exists in a DCS, MES, ERP, and elsewhere at different hierarchical levels and in different forms. In the time of computerization it is essential to have the capability to share internal and external data with different systems. In other words, open data interfaces are required.

In response to the focus on development towards open data interfaces, multiple new technologies have been incorporated into the CENTUM CS 3000. At the core of these technologies is OLE for Process Control (OPC). OPC is a standard specification of communication interfaces in the process automation (PA) and factory automation (FA) industries. Via an OPC interface, other vendors' DCSs and programmable logic controllers (PLCs) can be connected to a CENTUM CS 3000 system. The CENTUM CS 3000 uses OPC technology for the following functions:

  • Embedding of ActiveX controls in graphic windows
  • Display of graphic windows in a World Wide Web browser

The incorporation of these new technologies, has meant that the CENTUM CS 3000 meets the requirements of the times by offering a truly "open data interface" that allows the internal data of a DCS to be accessed from the outside as well as enabling a DCS to access data from outside of itself.

OPC INTERFACE

Figure 3 Frow of ActiveX Controls Creation
Figure 3 Frow of ActiveX Controls Creation

OPC is based on Distributed Component Object Model (DCOM) technology that was proposed by Microsoft Corporation for Windows-based networks, and is a specification that stipulates the communication interface for networking environments for PA and FA. Many DCS, PLC, Plant Information and Management (PIM), and Supervisory Control and Data Acquisition (SCADA) vendors are participating in activities to draw up OPC specifications. Yokogawa is also participating in Japanese domestic and overseas OPC workgroups.

Traditionally, DCS and PLC vendors prepared the vendors' original interfaces for upper-level systems. As shown in Figure 1, each client therefore needed to prepare a specific interface for each DCS and PLC. This troublesome necessity of multiple interfaces has had the effect of hampering the increase of mutual connections.

Figure 2 shows client/server architecture with the incorporation of OPC technology in DCSs and PLCs. In this architecture, each client is only required to have an OPC interface to access data in the DCSs and PLCs of all vendors via an OPC server inside each of the DCSs and PLCs. It is only natural, that such a simple requirement will help increase mutual connections and open systems.

OPC Server of CENTUM CS 3000

For the purpose of providing an open data interface as aforementioned, we have developed an OPC server that runs on a human interface station (HIS) of the CENTUM CS 3000 and conforms to OPC Specifications of the OPC Foundation, as shown in Tables 1 and 2.

Table 1 OPC Server Specifications of OPC Foundation

DA2 OPC Data Access Specification 2.0
HA1 OPC Historical Data Access Specification 1.0
AE1 OPC Alarm & Event Specification 1.0

The CENTUM CS 3000 supplies various process data to upper-level systems via the OPC server. To enable each client to access almost any kind of data in the CETUM CS 3000, custom interfaces are added to the interfaces defined in OPC Specifications, as shown in Table 2. We will propose to OPC workgroups that these custom interfaces be incorporated into standard interfaces in OPC Specifications.

Table 2 Compliance of CENTUM CS 3000's OPC Server

Accessed Data Access Conforming to (Ref. Table 1)
Current values Read/Write DA2
Tag information Read DA2
Tag list Read DA2
Station list Read DA2
Historical tread data Read HA1
Summary data Read HA1
List of trend data to be acquired Read HA1
List of data to be summarized Read HA1
Alarm event message notification Read AE1
Alarm event message generation Read Custom
Batch data Read/Write Custom
Historical messages Read Custom
Recipe list Read Custom
Information of data of batch common data block Read Custom
List of information of data of batch common data block Read Custom

Security

Figure 4 Data Flow
Figure 4 Data Flow

In the CENTUM CS 3000, security settings have been enhanced to fill security holes that existed with the insufficient security provided with DCOM. This enables detailed security settings to be made for each client. For example, it is possible to permit only client A to write the SV of FIC100 and only client B to read the PV of TIC200.

Traffic Control

For an OPC server in a DCS, care must be taken that the operation and monitoring functions are not affected by large amounts of data being accessed for reading and writing too frequently. CENTUM CS 3000's OPC server does not permit access for more than a specified amount of data within a specified time in order to limit the load on each HIS and field control station (FCS) and V-net communication load, thus assuring steady plant operation.

ACTIVEX CONTROLS AND CONTAINERS FOR GRAPHIC WINDOWS

Figure 5 Example of System for Browsing HIS's Graphic Windows
Figure 5 Example of System for Browsing HIS's
Graphic Windows via a Web Browser

Graphic windows of HIS are provided with extensive primitives to allow the building of operation and monitoring windows suitable for the needs of each user.

Graphic Container

In OLE terminology, the word container means a file containing linked or embedded objects. As a new feature, ActiveX controls can be embedded in HIS graphic windows. (See Figure 3.) This feature, referred to as graphic container, offers the following advantages:

  • Allows the user to add desired, specialized functionality to a graphic window
  • Allows the user to create most animated graphic windows of rich representations

ActiveX controls can be written in a variety of programming languages, including C, C++, Visual Basic, and Java. For example, process data can be obtained via an OPC server and easily processed using an ActiveX control. Also, various forms of presentation including graph displays and DYNAMO-flow diagrams can be added to HIS graphic windows using ActiveX controls supplied from a third party. Since the properties of each ActiveX control can be set using the Graphic Builder, a user- created ActiveX control can be used in different windows for different projects by changing the properties.

Graphic Interface

Control for ActiveX Controls The graphic interface control enables the user to create ActiveX controls to be embedded in a graphic window. Using properties, methods, and events provided by the graphic interface control (part of these are shown in Table 3), the user can create ActiveX controls well fitted to HIS graphic windows.

Table 3 Properties, Methods, and Events Provided by Graphic Interface Control

Properties HIS station name
HIS window name
Keyboard-focus state of window
Method Start/stop request
Request to the move the arrow-shaped cursor
Request to display a confirmation dialog box
Request to display an error message dialog box
Request to execute the function assigned to a function key
Request to change an LED status
Request to change the buzzer status
Request to read/write a graphic generic name
Event Synchronization event of timing to draw blinking
Periodic event of a window
Move of the arrow-shaped cursor event
Function key event
Change of keyboard-focus status of window

 

Figure 6 Function Configuration
Figure 6 Function Configuration

The graphic interface control itself is also supplied as an ActiveX control and hence it can be used in Visual Basic and other programming languages just like other controls. When creating an ActiveX control, allot the icon of a graphic interface control object in a window, then read and write the properties, methods, and events of that object. This icon is invisible at runtime.

User-created ActiveX controls can also exchange data directly with a graphic window container; however, use of the graphic interface control has the following merits:

  • Reduction of man-hours for creating ActiveX controls
  • Support of debugging in Visual Basic
  • Future expandability

In Visual Basic, the graphic interface control acts almost the same as it does during runtime. Hence, ActiveX controls can be debugged easily.

The graphic interface control and graphic window exchange data via the Component Object Model (COM) interfaces with each other in order to prevent the performance from being degraded when multiple ActiveX controls are embedded in a graphic window (see Figure 4).

DISPLAY OF GRAPHIC WINDOWS IN A WEB BROWSER

Figure 7 Process Flow
Figure 7 Process Flow

Software enabling CENTUM CS 3000's graphic windows to be displayed in a Web browser such as Internet Explorer and Netscape Navigator on a general-purpose personal computer has been developed. Traditionally, data and displays of a DCS were presented to the plant operators, but rarely disclosed to personnel in other departments. However now, there is the demand for a system solution of information sharing in a company, which allows, for example, access by management to data accumulated in a DCS. Using this software, CENTUM CS 3000's graphic windows can be browsed and viewed anytime anywhere via a Web browser.

Advantages

  • The only requirement is access to any type of PC that is capable of running a Web browser to display graphic windows.
  • Effective use of the intranet (no need of new cabling)
  • Integration of leading-edge Internet technologies with a DCS system

An example is given in Figure 5. A Web browser runs on client PCs and displays the HIS's graphic windows. Process data is collected from the HIS via the WWW server. Since client PCs do not directly access the HIS in this configuration, the safety integrity of the DCS system is secured.

Overview of Actions (See Figure 6)

Using this software, the user can view in any desired Web browser, almost the same windows as the CENTUM CS 3000's graphic windows. This is made possible by converting each graphic object file of the CENTUM CS 3000 into a Java applet.

  • Drawing Primitives:
    Each Java applet supports functions equivalent to those of the CENTUM CS's graphic windows.
  • Data Acquisition:
    Process data is collected via the Data Source Server running on the WWW server from an OPC server running on an HIS.
  • Security:
    For security, it may be desired to permit only authorized users to access DCS's windows. In this case, security can be set for each Web page so that the graphic windows will only be displayed when a key-code floppy disk is inserted into the computer.

Process Flow (See Figure 7)

  • Graphic Object Conversion:
    - Converts graphic object files of the CENTUM CS 3000 into Java source files.
    - Creates Java applets from converted Java source files using a Java compiler available on the market.
  • Running Java Applet:
    - Java applets draw graphic primitives and acquire process data. Since a user who views these Java applets does not actually operate the plant, Java applets perform data acquisition only when run and do not update the displayed data periodically. To display the updated data, the user must click the button designated by the Web browser. In Netscape Navigator this is the Reload button and in Internet Explorer this is the Update button.
    - Graphic windows displayed in a Web browser are used only for monitoring and cannot be used for operation.
  • Data Source Server:
    - The Data Source Server is a server that interfaces Java applets with an OPC server by converting the OPC interface protocol to its unique TCP/IP socket interface protocol.
    - The Data Source Server runs as a service under Windows NT.

CONCLUSION

In order to meet the needs of the times, we must pursue new technologies and incorporate them into the CENTUM series of core products wherever appropriate. By keeping our eyes on the development of new technologies we aim to continue introducing new attractive products in the future.

Furthermore, as a major DCS vendor, we are committed to using our extensive expertise in a positive way to help with the activities of stipulating OPC interface specifications.

  • Windows, Windows NT, ActiveX, Visual Basic, C++, OLE, and Internet Explorer are registered trademarks of Microsoft Corporation, USA.
  • Netscape is a registered trademark of Netscape Communications Corporation.
  • Java is a registered trademark of Sun Microsystems, Inc.
  • Other product and company names appearing in this report are trademarks or registered trademarks of their respective holders.

Industrien

  • Biomass Power

    Biomass is increasingly in the news these days as it is a renewable energy source that can help thermal power plants reduce their carbon dioxide emissions. 
    Yokogawa systems are used all over the world in all types of power plants, including those that use biomass. Yokogawa measurement and control technologies make it possible for these plants to operate more efficiently and reduce their carbon footprint.

    Mehr anzeigen
  • Bulk & Petrochemical

    Whether you produce petrochemicals, inorganics or intermediates, chemical companies are under cost and margin pressures to deliver products in a timely and efficient manner while maintaining safe and compliant operations. Additionally, chemical companies need to adjust to fluctuating feedstock and energy prices and to provide the most profitable product mix to the market.

    Yokogawa has been serving the automation needs of the bulk chemical market globally and is the recognized leader in this market. With products, solutions, and industry expertise, Yokogawa understands your market and production needs and will work with you to provide a reliable, and cost effective solution through the lifecycle of your plant.

    Mehr anzeigen
  • Power

    In the mid 1970s, Yokogawa entered the power business with the release of the EBS Electric Control System. Since then, Yokogawa has steadfastly continued with the development of our technologies and capabilities for providing the best services and solutions to our customers worldwide.

    Yokogawa has operated the global power solutions network to play a more active role in the dynamic global power market. This has allowed closer teamwork within Yokogawa, bringing together our global resources and industry know-how. Yokogawa's power industry experts work together to bring each customer the solution that best suits their sophisticated requirements.

    Mehr anzeigen
  • Water & Wastewater

    Water resources are finite, and therefore contributing to a sustainable water cycle is one of the Sustainable Development Goals (SDGs). Yokogawa has been providing advanced digital control solutions for the stable supply of clean and safe water, wastewater treatment for protecting the water environment, water loss management and optimization of plant operation for reducing CO2 emissions and running costs. With our leading-edge technologies, dependable products and extensive expertise and experience of diverse water projects around the world, we work with you to provide sustainable water solutions that boost your business and add value throughout the plant lifecycle.

    Yokogawa supports a wide range of water control applications in both the municipal and industrial water markets.

      

     

    Mehr anzeigen

Zugehörige Produkte & Lösungen

  • Prozessleitsysteme (PLS)

    Unser verteiltes Steuerungssystem (DCS) ermöglicht die Automatisierung und Steuerung industrieller Prozesse und verbessert die Geschäftsleistung. Über 10.000 Anlagen vertrauen auf das Yokogawa DCS, um ihre Produktionsziele zu erreichen.

    Mehr anzeigen

Top