With the 2-loop control of the UT75A, can I stop/run loop 1 and loop 2 separately?

Yes. With 2-loop control, you can switch each loop between stop and run separately.
Change the setup parameter CTL > SR2L to SEP.

SR2L settings:

  • COM: Common operation for both loops (default)
  • SEP: Separate operation for each loop

Prodotti e Soluzioni Correlati

  • Advanced Application UT75A

    The UT75A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT75A also support open networks such as Ethernet communication.