Up to how many SSRs can be connected to the UT?

The UT's voltage pulse specifications are: ON voltage 12 VDC or more; load resistance 600 Ω or more; ON voltage 0.1 VDC or less. For example, in the case of the Omron G3PH (operating voltage DC4-30 V, input current 5 mA or less), up to 4 units can be connected in parallel. To drive an SSR with the UT, use voltage pulse output. Since the current flowing will be 12 V/600 Ω=20 mA, this satisfies the above conditions.

ilgili Ürünler & Çözümler

  • Advanced Application UT75A

    The UT75A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT75A also support open networks such as Ethernet communication.

    Daha Fazla Gör
  • Mid-level UT55A/UT52A

    The UT55A and UT52A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT55A/UT52A also support open networks such as Ethernet communication.

    Daha Fazla Gör
  • UT32A-D

    The UT32A-D is a compact digital indicating controller with selectable 2-loop control. It also includes a ladder sequence function.

    Daha Fazla Gör
  • UT35A/UT32A

    The UT35A and UT32A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT35A/UT32A also support open networks such as Ethernet communication.

    Daha Fazla Gör

En üst