I set up the SMARTDAC+ GX/GP series' SLMP communication, but communication isn't working. When I look under Factor in the SLMP Communication Status screen and the SLMP Log screen, ERROR: 4031 appears in a yellow diamond.

SLMP communication errors appearing in yellow are all error code responses from the PLC side. ERROR 4031 is a “CPU device specification” error. Check whether the specified device is within the range. Note that SLMP device start numbers are specified in hexadecimal.

Related Products & Solutions

  • Modular GM10

    For industrial and lab applications, the GM10 offers Bluetooth wireless connection and modular I/O that offers accurate and reliable measurements.

    See More
  • Touch Screen GP10/GP20

    SMARTDAC+TM GP10/GP20 is a paperless recorder that provides intuitive, human-centric design, web-enabled functionality, and scalable architecture.

    See More
  • Touch Screen Paperless Recorder GX10/GX20

    The SMARTDAC+TM GX10/GX20 is a panel mount paperless recorder with a modular architecture on the back panel and has a data logging function to acquire the required data. By supporting not only I/O but also many communication protocols, you can connect to various devices. GX utilizes AI. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.