At the end of UP32A/UP35A/UP55A programs, does the PIDNo. change when local is set (JC=LOCAL)?

If you set JC=LOCAL, local operation status begins when the last segment of program operation ends. In this case, when zone PID (ZON=1,2,4) is selected, the PID group switches according to the selected zone. When segment PID (ZON=0) is selected, the PID group switches according to the selected local PID number (L.PID).