Introduction

Power plant boiler houses are designed to burn coal or high sulfur oil. Federal and State pollution regulations require power plant boiler houses to “scrub” (remove) sulfur dioxide (SO2) from flue gases to fulfill emission limits. SO2 in flue gases is known to be harmful to the environment as it is one contributor to the formation of acid rain. pH control is critical for the proper functioning of the scrubber system. Flue gas desulfurization (FGD) technology, commonly referred to as a scrubber, is a proven and effective method for removing sulfur dioxide emissions from the exhaust of coal-fired power plants.

Scrubber System

The basic principle of a sulfur dioxide scrubber system is the removal of SO2 by using its chemical characteristics to combine with water. In some cases, parallel rotating rods create a series of short-throat Venturi openings. A series of low pressure, large orifice spray nozzles direct the scrubbing solution into the system. “Scrubbing liquor” is introduced into the system with the flue gas stream. Depending on the scrubber design, the gas can flow either concurrent (with) or counter-current (against) the scrubbing liquor. The high velocity turbulence caused by the Venturi openings ensures maximum gas to liquid contact. Here, the droplets absorb the SO2 and impact and drop particulates out of the stream. The scrubbed gas is then sent through a demister or re-heater to prevent condensation and exhaust to the atmosphere. The scrubbing liquor can be bubbled through a slurry of either lime (Ca(OH)2) or limestone (CaCO3) and water. Either lime or limestone will combine with the sulfite ions from the flue gas to form gypsum, CaSO3. The SO2 captured in a scrubber combines with the lime or limestone to form several by-products. A primary by-product is calcium sulfate, commonly known as gypsum. Spent scrubbing liquids are sent to a clarifier, where the insoluble gypsum is removed, and the water is returned to the scrubber system. The addition of lime or limestone to the scrubbing solution is controlled by monitoring the pH of the solution. Lime slurries are generally alkaline, with a control point near pH 12, while limestone slurries are more neutral.

Scrubber

pH Control

A pH measurement is one of the testing methods used to monitor the continuous blowdown and replenishment. The SO2 within the scrubbing gases can be controlled by maintaining the level of caustic scrubbing chemicals that are commonly used. pH is a critical factor for the proper operation of a scrubber. It is also difficult to measure due to 2-15% solids and tendencies towards scaling, coating, and plugging.

pH Concentration graph

The CaSO4 concentration decreases slightly as pH decreases. Furthermore, because the dissolved oxygen concentration in the slurry is constant, sulfate formation depends only on the concentration of SO3. The precipitation of CaSO4 increases as pH decreases. Thus CaSO4 is apt to form scale at a lower pH. Hard scale formation can be controlled by keeping the pH high. The solubility of CaSO3 increases significantly as pH decreases, or conversely, CaSO3 forms a precipitate as pH increases. If the pH is too high, “soft pluggage” occurs. Soft pluggage is due to the formation of calcium sulfite precipitates, which appear as large leaf like masses. Maintenance of equipment that has a soft pluggage is more manageable than equipment that has a hard scale. In many cases where soft pluggage has occurred, it can be melted off simply by lowering the pH (increasing solubility). It is obvious that a potential dilemma exists; operation at too low pH promotes the formation of hard scale, and operation at too high pH promotes the formation of soft pluggage. Only through experience can the proper pH range be determined. Typically, limestone is added to achieve the desired level of SO2 removal based on the sulfur content of the coal, the boiler load, and the monitored SO2 concentration of the flue gas while maintaining the pH in the reaction tank at 5.5 to 6.0 pH. The pH sensor can be located in the re-circulating tank or line.

Conductivity Control

Conductivity is one of the most common testing methods to monitor the concentration of scrubbing chemicals and by-products. As the concentration of the scrubbing chemical is depleted, its contribution to the total conductivity value will also decrease. However, simultaneously, the contribution to conductivity from the by-products is increasing. Therefore, a measurable decrease in conductivity is detected as the scrubbing solution is depleted. However, difficulties can arise when more than one gas is scrubbed. Different by-products will be formed depending upon the relative proportions of the gases, leading to variations in the conductivity background. Although a conductivity measurement can be difficult or impossible, it may still provide a useful alarm point to alert the operator to check a grab sample. In scrubbers where the scrubbing chemical concentration is maintained by continual replenishment and blowdown, conductivity can initiate blowdown to prevent high dissolved solids buildup. In continual replacement scrubbers, conductivity can initiate blowdown to prevent high dissolved solids buildup. Toroidal or Inductive conductivity is the best measurement form in this application, and the sensor should be located where it will be exposed to a representative sample.

Product Recommendations

pH Measurement System

Transmitter

FLXA202 /FLXA21 2-wire pH/ORP measurement system FLXA402 4-wire pH/ORP measurement system

Sensor

Option 1: FU20/FU24 pH/ORP Combination electrode

Option 2: FF20 Flow-thru assembly with seperate measure, reference and temperature electrodes. i.e. SM21-AG4, SR20-AP24 and SM60-T1; SC21C- AGC55 and SM60-T1

Option 3: FU20-FTS pH/ORP Differential pH electrode

Conductivity Measurement System

Transmitter

FLXA202 /FLXA21 2-wire pH/ORP measurement system

FLXA402 4-wire pH/ORP measurement system

Sensor

ISC40 Inductivity Conductivity electrode with various installation options(insertion, flow through, retractable).

Configurations

pH & conductivity configurations

Option1/3 & Conductivity Configurations

Option 2 Configurations

 

Industries

  • Energie

    Dans les années 1970, Yokogawa est entré dans le secteur de l'énergie avec le lancement du système de contrôle électrique EBS. Depuis lors, Yokogawa a poursuivi avec constance le développement de ses technologies et de ses capacités afin de fournir les meilleurs services et solutions à ses clients dans le monde entier.

    Yokogawa a exploité le réseau mondial de solutions énergétiques pour jouer un rôle plus actif sur le marché mondial dynamique de l'énergie. Cela a permis un travail d'équipe plus étroit au sein de Yokogawa, en rassemblant nos ressources mondiales et notre savoir-faire industriel. Les experts de Yokogawa dans le domaine de l'énergie travaillent ensemble pour apporter à chaque client la solution qui répond le mieux à ses besoins spécifiques.

    Voir plus

Les produits et solutions liés

  • 2-Wire Transmitter/Analyzer FLXA202

    The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.

    Voir plus
  • 2-Wire Transmitter/Analyzer FLXA21

    The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.

    Voir plus
  • Differential pH/ORP Sensors

    The cation differential pH and ORP sensors were designed for difficult applications where conventional sensors are ineffective. These include measurements such as brine solutions to applications as diverse as electrolysis processes and cheese manufacturing.

    Voir plus
  • Flow/NPT Fittings FF20/FS20

    Yokogawa has invested considerable design and development time in producing a full range of fittings with particular emphasis on designs that reduce installation and maintenance time and consequently save operation costs.

    Voir plus
  • pH and ORP Sensors

    pH electrodes and sensors are the sensing portions of a pH measurement. Various installation options including retractable, flow thru, immersion, and direct insertion. Proper pH electrode/sensor selection is critical for optimal measurement results.

    Voir plus

Haut