When writing SMARTDAC+ GX/GP/GM I/O channel data to an SLMP server using SLMP communications, how should I set the first and last channels?

When writing I/O channel data using SLMP communications, specify channels within the same module for the first and last channels of the SLMP communication command. When writing data from multiple modules, use different command numbers for each module.

Example To write 30 ch of data from CH0001–CH0210,
   Command no. 1: CH0001–CH0010
   Command no. 2: CH0101–CH0110
   Command no. 3: CH0201–CH0210

Les produits et solutions liés

  • Modular GM10

    SMARTDAC+TM GM10 data logger has a modular architecture that can acquire necessary data. By supporting not only I/O but also many communication protocols such as 920MHz wireless, Modbus and so on. Monitor and setting changes are available through Bluetooth. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.

    Voir plus
  • Touch Screen GP10/GP20

    The SMARTDAC+TM GP10/GP20 is a portable paperless recorder with a modular architecture on the back panel and has a data logging function to acquire the required data. By supporting not only I/O but also many communication protocols, you can connect to various devices. GP utilizes AI. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.

    Voir plus
  • Touch Screen Paperless Recorder GX10/GX20

    The SMARTDAC+TM GX10/GX20 is a panel mount paperless recorder with a modular architecture on the back panel and has a data logging function to acquire the required data. By supporting not only I/O but also many communication protocols, you can connect to various devices. GX utilizes AI. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.