My voltage and current measurements on the power monitor are correct, but power integration either doesn't occur, or the values are small. How do I check whether the measured values are abnormal?

Check the active power. If the active power turns negative or extremely small, check the items below. The active power is negative when the power is regenerating.

Active power check items

Items to check

  1. Is the CT attachment orientation correct?
  2. Is a CT connected to the R and T phases?
  3. Is the R phase CT connected to 1S and 1L, and is the T phase CT connected to 3S and SL? Also check the polarity (k, l) on the CT secondary side.
  4. Are R, S, and T wired to P1, P2, and P3?

Check the wiring and attachment for other phase and wiring schemes as well.

Zugehörige Produkte & Lösungen

  • Leistungsüberwachungssystem SMARTDAC+ GM / UPM100

    Das Leistungsüberwachungssystem SMARTDAC+ GM/UPM100 ist eine Lösung zur Überwachung des Stromverbrauchs. Sie besteht aus dem 920-MHz-Leistungsüberwachungsgerät UPM 100 und dem GM-Datenerfassungssystem. Das System bietet eine benutzerfreundliche Visualisierung des Stromverbrauchs in der Anlage (Diagramme), ermöglicht das Erstellen von Berichten usw. Unsere Lösung kann Ihnen dabei helfen, Anlagenteile zu identifizieren, die zu einem erhöhten bzw. verschwenderischen Stromverbrauch neigen.

  • PR201 Power Monitors

    The PR201 Power Monitors was discontinued on 1/01/2006. The PR300 is a replacement product.

  • UPM100/UPM101

    Das UPM100/UPM101 ist ein kompaktes Leistungsüberwachungsgerät, das die Messung von 15 verschiedenen Leistungs- und Energiewerten mit nur einem einzigen Gerät ermöglicht.

  • UZ005 Power Monitors

    The UZ005 Power Monitors was discontinued on 9/01/2006. The PR300 is a replacement product.


Top