What is the output during burnout for the DT5, DR5, DM1, and DS1?

The output behavior when the input is disconnected for the burnout setting is as follows.
All four models have a variable output range of -10 to 110% (-5% to 105% for the ±10 V range).
Therefore, the output at burnout is as follows.

  • For burnup, the output can be 110% or more (or 5.4 V or more for 1–5 V outputs).
  • For burndown, the output can be -10% or less (or 0.6 V or less for 1–5 V outputs).
  • For off, the output will be undefined, so it is unknown what will happen.