There's no output with a thermocouple temperature converter. What should I do?

  1. Check the power supply wiring.
  2. Check whether the power supply voltage meets the specifications.
  3. Confirm that the accessory RJC sensor is connected to the input terminal.
  4. Short the input terminals, then confirm that the output is equivalent to the terminal temperature.
  5. If the output signals is of the current specifications, attach an external 250 Ω resistance and measure the voltage.

Related Products & Solutions

  • JUXTA D Series Signal Conditioners

    The D Series is DCS-supported signal conditioners, consisting of modular type signal converters with versatile I/O specifications and housing nest. JIS and EIA conformed mounting nests come with terminal blocks for field wiring, connectors for DCS connection, and connectors for communications.

    See More
  • JUXTA F Series Signal Conditioners

    F Series signal conditioners are compact, space-saving (24 mm width) signal conditioners with front panel terminals. The microprocessor based models provide field configuration capability and minimum stock of spares. The installation is either DIN-Rail, Rack or Wall mounting, and the power supply is 24 V DC.

    See More
  • JUXTA M Series Computing Units

    M Series computing units include a type that supports user-specified programs, and types that support analog memory, peak/bottom holders, moving averages, dead times, temperature/pressure compensation, and a wide range of other applications.

    See More
  • JUXTA M Series Signal Conditioners

    M Series signal conditioners are a plug-in type that can support a wide range of applications through a versatile I/O specifications. Plug-in type construction provides easy for instrumentation planning, field wiring and maintenance. Over 30 types of signal conditioners are lined up in M Series.

    See More
  • JUXTA VJ Series Limit Alarms

    The VJ series limit alarms are compact, plug-in type alarm setting devices with easy-to-use functions. Four models are available: the VJAK for 2-wire system transmitters; the VJHK with DC voltage/DC current inputs; the VJRK with RTD inputs; the VJTK with thermocouple inputs; and the VJUK with universal inputs.

    See More
  • JUXTA VJ Series Signal Conditioners

    Compact size, plug-in style and microprocessor based high performance capabilities (Multi-function types) makes the VJ Series Signal Conditioners an excellent choice for almost every application. Analog output, Hi-Low alarm relay outputs or RS-485 MODBUS communication is available as optional second output.

    See More
  • JUXTA W Series Signal Conditioners

    Compact size, versatile mounting, and microprocessor based high performance capabilities makes the W Series an excellent choice for almost every application. The specifications of W Series signal conditioners are as same as F Series signal conditioners except for power supply voltage, second output and case width.

    See More

Top