Duct Fire Detection

"Quick detection of fire in rolling mills due to accumulation of oil residue inside fume ducts"

 

Customer Concerns

Risk of fire in rolling mills due to accumulation of oil residue inside fume ducts

In rolling mills, rolling oil is sprayed on the rollers to reduce friction and stabilize product quality. Most of the rolling oil is circulated and reused, but a small portion evaporates. The oil vapor, together with dust and other materials, is sucked up into a fume duct mounted directly above the rollers, and is then treated with a dust collector.

Over time, oil residue builds up on the inside surface of the fume duct and is dried by exposure to high temperature gasses, making it highly flammable even at relatively low temperatures. Any contact with an ignition source such as an electrostatic spark can cause this residue to catch fire, and in the worst case such a fire originating in the duct can spread throughout the structure.

Most fume ducts are cleaned periodically, but some locations high up inside the ducts can be difficult to access and clean well, making it difficult to entirely eliminate the risk of fire. It is also nearly impossible to manually monitor conditions inside these ducts.

Fume ducts play an essential role in rolling mills, and the breaking out of a fire inside such an installation can have an adverse impact on a company’s bottom line by causing an unplanned plant shutdown.

 

Risk of fire in rolling mills due to accumulation of oil residue inside fume ducts

 

The Solutions and the Benefits

24/7/365 temperature monitoring in difficult to access locations

When its optical fiber sensor cable is installed on surface of a fume duct, the Yokogawa DTSX distributed temperature monitoring sensor is able to quickly detect any abnormal rise in temperature inside the duct. Around the clock and year-round, the DTSX is able to monitor temperature even in those locations that are too narrow or too high up for human operators to access.

Minimizing fire damage through early detection of abnormal overheating

The amount of damage caused by a fire will depend in part on how long it takes to detect it and determine its exact location. As many rolling mills are unmanned operations, the fire response at such facilities tends to be delayed. The DTSX is an ideal solution for such problems: with a resolution of just one meter, it is able to pinpoint the location of a heat buildup in as little as 10 seconds.

Together with this solution, Yokogawa provides its customers monitoring screens and reporting functions that are customized based on their specific requirements.

 

Cable laying example on fume duct surface (Top view)

 

How DTSX Works

Measuring the intensity of Raman scattered light
Using pulses of laser light beamed through an optical fiber cable, the DTSX is able to detect temperature-dependent variations in signal frequency that are the result of a phenomenon known as Raman scattering that occurs along the entire length of the optical fiber cable, and it also can determine the locations of those temperature readings using light that is bounced back (backscattering) to the source.

Example: Along a 6,000 meter optical fiber cable, nearly 6,000 measurement points
By measuring how long it takes light to make a round trip back to the source (backscattering), the DTSX is able to calculate the location for each temperature reading. Abnormalities can be located with a spatial resolution of just one meter.

Temperature monitoring using optical fiber cable​​​​​​

Raman backscattering

 

Looking for more information on our people, technology and solutions?

Contact Us

Productos y Soluciones Relacionadas

  • DTSX1 Fiber Optic Heat Detector

    DTSX1 stores the functions required for heat detection in one box. DTSX1 analyzes the temperature data with high accuracy by measuring with fiber optic sensor cable and perform high temperature heat detection.

    Leer Más
  • DTSX200 Distributed Temperature Sensor

    The DTSX200 is a standard version that is ideal for temperature measurement, for medium-sized areas, and for areas where the distance of fiber optic sensor cables is short. It has excellent environmental resistance because it consumes less power and is less dependent on the temperature measurement environment.

    Leer Más
  • DTSX3000 Distributed Temperature Sensor

    The DTSX3000 is a distributed temperature sensor developed in response to the demand that “one unit be used to monitor temperature distribution a longer distance and a wider area”. A flagship model that meets the expectations for long-distance temperature measurement and high temperature resolution.

    Leer Más
  • Fiber Optic Temperature Sensor DTSX

    The DTSX fiber optic temperature sensor, which uses optical fiber for the temperature sensor, quickly detects and locates abnormalities in equipment by monitoring temperatures at production facilities located far away and across wide areas 24 hours a day, without omission. Highly accurate predictive maintenance avoids downtime and ensures stable plant operation.

    Leer Más