If using the product's reference junction compensation function with GX90XA module thermocouple inputs, do not install a "GX90XA-10-C1" mA module or "GX90WD" digital input module into the slot to the right* of the GX90XA module (the side with the smaller slot number). If you install those modules there, RJC accuracy cannot be guaranteed.
*When looking from the back panel of the GX/GP main unit or the front panel of an expansion unit.
Productos y Soluciones Relacionadas
-
Touch Screen GP10/GP20
The SMARTDAC+TM GP10/GP20 is a portable paperless recorder with a modular architecture on the back panel and has a data logging function to acquire the required data. By supporting not only I/O but also many communication protocols, you can connect to various devices. GP utilizes AI. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.
-
Touch Screen Paperless Recorder GX10/GX20
The SMARTDAC+TM GX10/GX20 is a panel mount paperless recorder with a modular architecture on the back panel and has a data logging function to acquire the required data. By supporting not only I/O but also many communication protocols, you can connect to various devices. GX utilizes AI. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.