It depends on the mode.
In 10 ch mode, measurement can occur on CH1-CH10; in 2 ch mode, CH1-CH2.
In 10 ch mode, A/D integral time is fixed at 1.67, and measured values (especially with temperature measurements from thermocouples) may fluctuate because power-line period noise is not eliminated. In 2 ch mode, A/D integral time is fixed at 16.67, and power-line period noise can be eliminated.
For operation mode settings, see the user's manual (IM 04L51B01-01EN)
◊1.7.3 "Setting the Operation Mode for a Module."
User's Manual (IM 04L51B01-01EN)
Productos y Soluciones Relacionadas
-
Touch Screen GP10/GP20
The SMARTDAC+TM GP10/GP20 is a portable paperless recorder with a modular architecture on the back panel and has a data logging function to acquire the required data. By supporting not only I/O but also many communication protocols, you can connect to various devices. GP utilizes AI. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.
-
Touch Screen Paperless Recorder GX10/GX20
The SMARTDAC+TM GX10/GX20 is a panel mount paperless recorder with a modular architecture on the back panel and has a data logging function to acquire the required data. By supporting not only I/O but also many communication protocols, you can connect to various devices. GX utilizes AI. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.