Boiler Combustion Air Flow Measurement

Introduction

Draft is the differential caused by the flow of hot gas through a furnace. On a vertical petrochemical heater, it is the differential between the furnace inlet (bottom) and the stack. This differential is caused by the restrictions of the tubes and the preheater in the bridge wall section before the stack. Draft will increase as firing rate increases and will decrease as firing rate decreases. It is an indication of air flow through the burner throats or total gas flow through the furnace. 

Application

How Is Boiler Air Flow Measured? Boiler air flow (or air flow on a forced or balanced draft furnace) may be measured with a pitot tube, air foil section, or any calibrated flow restricting device located in the duct that leads from the forced draft fan to the windbox. (The windbox is the area behind the burner throats that supplies combustion air to the burners.) The differential across the windbox to the furnace can be as high as 25" H2O, but is not used because each time a register is adjusted, the flow relationship to delta P changes. On many boilers, air flow is the measured differential between the furnace inlet and the boiler outlet. This takes the differential of the hot gases as they flow through the furnace, across the convection section, and out the stack. In most cases, the differential ranges from 0.5 to 2.0 inches of water.

Boiler Combustion Air Flow Measurement

Errors From Drift and Zero Shift Most transmitters use a standard capsule, which may be selected for linearity, plus a high gain amplifier to achieve 4-20 mADC output for such a low differential. If the gain is ten, then any normal capsule errors are multiplied by ten. A capsule that has a ±0.1 drift now has a 1% drift. Since flow squared equals differential pressure caused by a flow restriction, the square root must be extracted, and at the low end, this 1% drift can cause a 10% flow error. If the transmitter is not designed to be sensitive at the low end, there will be a low end cut-off, usually at one percent.

Solution

Use DPharp! There are very few draft range transmitters that per- form well on this type of air flow measurement application. Yokogawa Industrial Automation's DPharp is excellent for this service since the zero is stable and it is not subject to temperature or static pressure drift, or zero shift, caused by the shock of furnace or boiler light-off.

DPharp EJA120A

  • DPharp EJA120A±0.1% Accuracy
  • Low ambient temperature effects
  • 0.4 inHPO minimum span
  • 0.01% Adjustment Resolution

 


 

Industries

Related Products & Solutions

EJA120A

Traditional-mount Differential Pressure Transmitter designed for Draft Range applications based on the EJA-A Series.

EJA120E

Traditional-mount Differential Pressure Transmitter designed for Draft Range applications based on the EJA-E Series.

EJX120A

Traditional-mount Differential Pressure Transmitter designed for Draft Range applications based on the EJX-A Series.

×