Boiler Combustion Air Flow Measurement

Boiler Combustion Air Flow MeasurementIntroduction

Draft is the differential caused by the flow of hot gas through a furnace. On a vertical petrochemical heater, it is the differential between the furnace inlet (bottom) and the stack. This differential is caused by the restrictions of the tubes and the preheater in the bridge wall section before the stack. Draft will increase as firing rate increases and will decrease as firing rate decreases. It is an indication of air flow through the burner throats or total gas flow through the furnace. 

Application

How Is Boiler Air Flow Measured? Boiler air flow (or air flow on a forced or balanced draft furnace) may be measured with a pitot tube, airfoil section, or any calibrated flow-restricting device located in the duct that leads from the forced draft fan to the wind box. (The wind box is the area behind the burner throats that supplies combustion air to the burners.) The differential across the windbox to the furnace can be as high as 25" H2O, but is not used because each time a register is adjusted, the flow relationship to delta P changes. On many boilers, air flow is the measured differential between the furnace inlet and the boiler outlet. This takes the differential of the hot gases as they flow through the furnace, across the convection section, and out the stack. In most cases, the differential ranges from 0.5 to 2.0 inches of water.

Errors From Drift and Zero Shift Most transmitters use a standard capsule, which may be selected for linearity, plus a high gain amplifier to achieve 4-20 mADC output for such a low differential. If the gain is ten, then any normal capsule errors are multiplied by ten. A capsule that has a ±0.1 drift now has a 1% drift. Since flow squared equals differential pressure caused by a flow restriction, the square root must be extracted, and at the low end, this 1% drift can cause a 10% flow error. If the transmitter is not designed to be sensitive at the low end, there will be a low-end cut-off, usually at one percent.

Solution

Use DPharp! There are very few draft range transmitters that perform well on this type of airflow measurement application. Yokogawa Industrial Automation's DPharp is excellent for this service since the zero is stable and it is not subject to temperature or static pressure drift, or zero shift, caused by the shock of furnace or boiler light-off.

DPharp EJA120A

  • DPharp EJA120A±0.1% Accuracy
  • Low ambient temperature effects
  • 0.4 inHPO minimum span
  • 0.01% Adjustment Resolution

 


 

Industries

  • Power

    In the mid 1970s, Yokogawa entered the power business with the release of the EBS Electric Control System. Since then, Yokogawa has steadfastly continued with the development of our technologies and capabilities for providing the best services and solutions to our customers worldwide.

    Yokogawa has operated the global power solutions network to play a more active role in the dynamic global power market. This has allowed closer teamwork within Yokogawa, bringing together our global resources and industry know-how. Yokogawa's power industry experts work together to bring each customer the solution that best suits their sophisticated requirements.

    See More

Related Products & Solutions

×

Have Questions?

Contact a Yokogawa Expert to learn how we can help you solve your challenges.


Top